American Power Conversion 200/208 V, 10-30 KVA Display Messages/Troubleshooting, Display messages

Models: 10-30 KVA 200/208 V

1 52
Download 52 pages 5.68 Kb
Page 23
Image 23

Display Messages/Troubleshooting

This section lists the status and alarm messages that the UPS might display. The messages are listed in alphabetical order, and a suggested corrective action is listed with each alarm message to help you troubleshoot problems.

Display messages

Display Message

Meaning

Corrective Action

 

 

 

Automatic Self Test

The UPS has started pre-programmed

No corrective action is necessary.

Started.

battery test.

 

 

 

 

Batt Temperature

The temperature of one or more bat-

Contact APC Customer Support.

Exceeded Upper Limit.

tery units has exceeded the system

See rear cover.

 

specifications.

 

 

 

 

Battery over-voltage

The battery voltage is too high and

Contact APC Customer Support.

warning.

the charger has been deactivated.

See back cover.

 

 

 

Bypass Not Available

The frequency or voltage is out of

Correct the input voltage to provide

Input Freq/Volt Out Of

acceptable range for bypass. This

an acceptable voltage or frequency.

Range.

message occurs when the UPS is

 

 

online, and indicates that the bypass

 

 

mode may not be available if

 

 

required.

 

 

 

 

Discharged Battery.

The UPS is in battery operation and

No corrective action is necessary.

 

the battery charge is low.

Shut down the system and the load

 

Note: Runtime is limited in duration.

equipment or restore incoming

 

 

voltage.

 

 

 

Emergency PSU Fault.

The redundant Emergency Power

Contact APC Customer Support.

 

Supply Unit (PSU) is not working.

See backcover.

 

The UPS will continue to work nor-

 

 

mally, but the PSU should be

 

 

replaced.

 

 

 

 

EPO Activated.

The Emergency Power Off switch has

Deactivate the Emergency Power Off

 

been activated.

switch.

 

 

 

Fan fault.

A fan has failed.

Contact APC Customer Support. See

 

 

back cover.

 

 

 

Int. Mech. Bypass

The internal mechanical switchgear is

No corrective action necessary. The

Switch Closed.

closed.

UPS is in internal mechanical bypass

 

 

operation.

 

 

 

Int. Mech. Bypass

The internal mechanical switchgear is

No corrective action is necessary.

Switch Open.

open.

 

 

 

 

990-2359A Smart-UPS® VT 10-30kVA, 200/208V and XR Battery Enclosure Operation Guide

15

Page 23
Image 23
American Power Conversion 200/208 V, 10-30 KVA manual Display Messages/Troubleshooting, Display messages