Mechanical Bypass
Mechanical Bypass Lever
For increased availability, the UPS is equipped with an internal mechanical bypass system providing mains power directly to the output, bypassing all UPS electronics.
CAUTION!
The load is not protected by the UPS when the internal mechanical bypass system is active, and, the power is not conditioned.
Turn into mechanical bypass
NOTE!
If the UPS is running and controllable through the display, carry out steps 1 through 6. If not, go directly to step 4.
Control | Display |
Status | Diags |
Setup | Help |
Logging |
|
Main Menu
From the Main Menu, select Control and press ENTER
Use UP/DOWN key to navigate to UPS into Bypass and press ENTER
Use UP/DOWN key to navigate to YES, confirm UPS into bypass, and press ENTER
Remove UPS Front Panel
SEE!
“Front Panel removal” on page 18.
25 |