Mechanical Bypass

Start-up is included with the UPS, and the start-up procedure described here is only applicable if the UPS requires a subsequent start-up.

Mechanical Bypass Lever

For increased availability, the UPS is equipped with an internal mechanical bypass system providing mains power directly to the output, bypassing all UPS electronics.

CAUTION!

The load is not protected by the UPS when the internal mechanical bypass system is active, and, the power is not conditioned.

Turn into mechanical bypass

NOTE!

If the UPS is running and controllable through the display, carry out steps 1 through 6. If not, go directly to step 4.

Control

Display

Status

Diags

Setup

Help

Logging

 

Main Menu

From the Main Menu, select Control and press ENTER

Use UP/DOWN key to navigate to UPS into Bypass and press ENTER

Use UP/DOWN key to navigate to YES, confirm UPS into bypass, and press ENTER

Remove UPS Front Panel

SEE!

“Front Panel removal” on page 18.

990-2359A Smart-UPS® VT 10-30kVA, 200/208V and XR Battery Enclosure Operation Guide