Battery Replacement

General safety prior to module replacement

WARNING!

• Only trained personnel familiar with the operation of the equipment, and the electrical and mechanical hazards involved, may install and remove system components.

The UPS and Battery Enclosure contain an internal energy source. Hazardous voltage may be present even when disconnected from the power source. Follow Total Power Off Procedure to completely de-energize the system.

Never replace batteries when the UPS is running in battery mode!

Risk of Energy Hazard, 96 V, 7.2 Ampere-hour battery. Before replacing batteries, remove all conductive jewelry such as chains, watches, and rings. High energy through conductive materials could cause severe burns.

Batteries do not contain serviceable parts. Do not open.

Do not open or mutilate batteries. Released material is harmful to the skin and eyes. It may be toxic. Do not dispose of batteries in a fire, as they may explode.

To ensure continuous battery back-up, only replace one Battery Module at a time.

For configurations that include customer-supplied external batteries, refer to manufacturer’s battery installation and maintenance instructions.

Two people to lift a component weighing between 18 – 32 kg.

Battery Module

One Battery Module consists of 4 Battery Units (max. 2 Battery Modules shipped in the Enclosures).

4 x 23kg

28

Smart-UPS® VT 10-30kVA, 200/208V and XR Battery Enclosure Operation Guide 990-2359A

Page 36
Image 36