51
9.0 Specifications

9.5 Battery Pack

Battery type: spill proof, maintenance free sealed lead-acid.
Nominal battery pack voltage: 48 Vdc.
Typical battery life: 3 to 6 years (depends upon number of discharge cycles and
normal ambient temperature).
Recharge time: see table in Section 9.9.
Max. number of Battery Packs: limited only by desired recharg e time.

9.6 Environment

Operating temperature: 0°C to 40°C (32°F to 104°F).
Storage temperature: -15°C to 45°C (5°F to 113°F).
Operating and storage relative humidity: 0 to 95%, non-condensing.
Operating elevation: 0 to 3,000 m (10,000 ft)
Storage elevation: 0 to 15,000 m (50,000 ft)
Electromagnetic immunity: IEC 801-2, 801-3, 801-4, 801-5; severity level III or IV.
Audible noise: < 55 dBA at 1 m (3 ft).

9.7 Physical

UPS dimensions (EU and IU mated): 17.8 H x 13.8 W x 17.8 D in.
(45.2 x 35.1 x 45.2 cm).
Battery pack dimensions: 9.1 H x 6.9 W x 17.8 D in. (23.1 x 17.5 x 45.2 cm).
UPS weight (EU and IU mated): 153 lb (69.4 kg), 191 lb (86.6 kg) for the 3000VA
and 5000VA models, respectively.
Electronics Unit (EU) weight: 40 lb (18.1 kg), 45 lb (20.4 kg) for the 3000VA and
5000VA models, respectively. Add 8 lbs (3.6 kg) for shipping independent of IU.
Battery pack weight: 64 lbs (29.0 kg). Add 5 lbs (2.3 kg) for shipping independent
of UPS.
Total shipping weight3000VA model: 256 lb (116.1 kg). Includes weight of
packaging, mated EU and IU, cords, and one (1) Battery Pack.
Total shipping weight5000VA model: 363 lb (164.6 kg). Includes weight of
packaging, mated EU and IU, cords, and two (2) Battery Packs.
Color: beige.

9.8 Approvals

Safety approvals: UL per 1778, CSA per C22.2., TUV per IEC 950
EMC verification: FCC, CDC, EN55022 Class A verified.