4.0 Installation
4.9 Output wiring procedure
As furnished, the UPS provides a total of eight IEC 320 C13 business appliance
receptacles for multiple small loads. To connect to these outlets, use the supplied
output jumper cords. These jumper cords replace the line cords supplied with your
computer equipment.

Jumper cord

Loads requiring more than 10 Amps must be hard wired to the UPS. To install output
wiring to the UPS, follow the below listed procedure.
4.9.1 If the desired power distribution plate knockout has not already been removed,
remove it now. See Section 4.7.2 for instructions on how to remove the knockout.
4.9.2 Fasten an appropriately sized and approved cable clamp (not provided) onto
the power distribution plate.
4.9.3 Strip insulation from the output cable wire ends at the length given in The
Electrical Cable Size table.
4.9.4 Thread the output cable through the cable clamp and through the power
distribution plate hole. Arrange the cable so that the end is near the output termina-
tions block.
4.9.5 Put the stripped wire end corresponding to Protective Earth into the termina-
tions block terminal marked PE and tighten the screw.