5.0 Operation
5.2.6 UPS Setup (continued)
30s delyThe on-battery audible alarm is disabled for
the first 30 seconds of on-battery operation.
Low BattThe audible alarm is disabled during on-
battery operation until low-battery conditions are reached.
DisableThe audible alarm is disabled during on-
battery operation and low-battery conditions.
For computer networks that are unable to issue UPS
shutdown commands during the last part of a shutdown
routine, the UPS provides a settable shutdown delay
interval to allow the network to finish its shutdown
routine.
 Shutdown delay choices are 20, 180, 300, and 600
seconds.
You may set a delay interval for energizing the output
after return of normal mains voltage, or after a scheduled
shutdown. This is useful in applications that require
staggered power up of equipment connected at various
sources.
 Load power delay choices are 0, 60, 180, and 300
seconds.
The user may select the UPSs nominal output voltage to
values of 220, 225, 230, or 240 Vac.
The UPSs nominal output voltage can be changed to
208V using optional power distribution plates (also called
PDUs, contact your dealer or the factory) regardless of
whether the input is configured for 208V or 240V service.
When an optional PDU is installed, the UPS must be set to
report the correct output voltage. When the Auto
function is chosen, the reported nominal output voltage is
scaled according to the input tap selected.