Specifications
Smart Distribution Panel with ATS 77
Environmental
Operating Temperature Range –5 to 40°C; The average temperature over a 24-hour period should not
exceed 35°C.
Operating Relative Humidity 5 to 95%, non-condensing
Operating Elevation 0 to 2000m
Storage Temperature Range –25 to 55 °C; The average temperature over a 24-hour period should
not exceed 70°C
Storage Relative Humidity 5 to 95%, non-condensing
Storage Elevation 0 to 15000m
Compliance
Safety Certified by VDE to IEC 60947-6-1 and 60439-1
CE Marking
Emissions EN 55011, Class A
VCCI, Class A
Immunity EN 50024
EN 61000-4-2, Level 4
EN 61000-4-3, Level 2
EN 61000-4-4, Level 4
EN 61000-4-5, Level 4
EN 61000-4-6, Level 3
EN 61000-4-8, Level 3
ANSI C62.41 Category A
ANSI C62.41 Category B