Display Interface
38 Smart Distribution Panel with ATS
Maintenance Record: Scroll through a list of items that accumulate after the
maintenance record is reset, including:
–Last Maintenance Date
–Operating Days
–Engine Starts
–Total kWh
–Total Runhours
Next Maintenance: View the month and year of the next scheduled maintenance and the
number of days until the scheduled maintenance, and clear the maintenance record so that
the data in the menu, Maintenance Record, is reset to zero.
Generator Settings The following settings are accessible through this screen:
Operating Settings
–Start Delay The amount of time that the generator waits after the start signal is
initiated before the generator starts and powers the load.
(Configurable on the generator control panel.)
–Stop Delay The amount of time between when the start signal is removed and
when the generator stops. (Configurable on the generator control
panel.)
–Crank Settings The following settings can be changed in the generator service
menus by generator service personnel.
Crank: Whether the crank cycle is enabled. If the crank cycle is
not enabled, the generator will attempt to start until the battery
dies.
Crank Cycles: The number of crank cycles that the generator
will go through when attempting to start the generator. The
default setting is three.
Crank Time: The amount of time that the generator will crank
during a crank cycle. The default setting is 15 seconds.
Rest Time: The amount of time that the generator will rest after
it cranks during a crank cycle. The default setting is 15 seconds.
Manufacturer Data
–Fuel System The type of fuel that the generator uses (default is diesel).
–Tank Size The size of the fuel tank on the generator (in Liters).
–Final Assy Date Date that the generator was assembled at the factory.
–Model Number Generator model number from Cummins®.
–GenSet S/N The serial number of the generator.
–Voltage Config Nominal input voltage (400V).
–Alternator Freq No minal frequency setting of the alternator output (50Hz).
–Gen kW Rating The power rating of the generator (88 kW, 131kW, 182kW).
Gen Output Adjust
–Voltage Displays the desired alternator output voltage (configurable on the
generator control panel).
–Frequency Displays the desired alternator output frequency (configurable on
the generator control panel).