84 Smart Distribution Panel with ATS
If Source 2 is a Generator that is Not an APC InfraStruXure Generator

Differences in your system from information presented in this manual

This manual assumes that Source 2 is an APC InfraStruXure Generator. If you have a generator other
than an APC InfraStruXure generator, some of the information in this manual will not apply to your
system.
The ATS is designed to work with the APC InfraStruXure Generator, and the ATS does not
communicate with other generators. In addition, other generators will operate differently than the
generators that are described in this manual. Disregard the following sections, as they do not apply to
your system:
• “Generator start se quence” on page 7
• “Genera tor cool-down” on page 7
• “Fuel monitoring/runtim e calculation” on page9
• “Commun ication converter” on page 13 (item 4)
• “Resetting automatic operation on the generator” on page 20
• “Genera tor” on pages 37–38
• “Fuel Alarm Limits” on page 44