GMT Fuse protected Load Connections

Connections for ¼ to 15 Amp DC loads require a ring terminal with a 0.170 in (4.3 mm) clearance hole and are located at the rear of the unit. Load Connections should be made as shown in Figure 3.7-2.

J2

-54 V

 

 

 

 

F2

F3

J3

F6

F1

 

F4

F5

J5

F8

F9

 

 

 

F12

F7

J4

F10

F11

 

54 V Rtn

 

Figure 3.7-2 Connections to GMT Fuses

3.8. Input / Output Connections

Relay Output Connections

There are three output relays available that provide outputs via Form “C” relay contacts. Two of these are pre-assigned as the Minor and Major relay outputs. The other output is designated as “Very Low Voltage”. The relay contacts should only be used to switch resistive loads of 0.5 amperes or less at 60 Volts or less. Figure 3.8-1 shows the alarm output connection designations. Whenever possible use the common and normally open contacts. If the alarm wiring gets pulled loose, or the controller is removed, you will get an alarm. The output relays energize when an alarm condition occurs. A cable (0W09050) is available to connect the output relays. See Figure 3.7-2 for details.