MX06-50 Temperature Probe Selection

Temperature compensation can be configured for either a Fahrenheit or Celsius probe by the use of configuration jumpers on pin header J4 shown in Figure 5.3-1. The MX06-50 is factory set for Fahrenheit operation, with jumpers on all position of J4.

5.4. MX06-100 Configuration Settings

The control card for the MX06-50 is different than the control card for the MX06-100 due to increased number of rectifiers in the MX06-100. The control card for the MX06 is the 0P9172 and for the MX06-100, the control card is the 0P9745. This section will deal with configurations applicable to the MX06-100 only.

 

 

 

 

 

 

GND

 

 

V-ADJ

 

 

 

 

 

E1

 

 

E8

 

 

 

 

 

 

 

 

BATT ALM GMT ALM

 

 

 

 

 

 

 

 

J4

J7

 

 

Factory Set. Do not touch.

 

J5

J8

 

 

 

J6

J9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(SEE MANUAL)

J1

K1

RECT SELECT

 

 

 

 

 

S2

 

ON: RECTIFIER NOT INSTALLED

 

 

 

 

 

 

OFF: RECTIFIER INSTALLED

 

 

 

1

 

 

 

10

 

 

 

 

 

 

 

RECT NUMBER

 

 

 

 

 

K4

 

K2

K3

 

 

 

 

 

 

 

 

R105

 

R106

 

R102

 

R103

R104

 

 

 

 

 

 

 

 

E12

DISCON LEV ADJ

E9

L V ALARM

 

 

E13

 

 

 

E10

E11

 

 

RECON LEV ADJ

 

 

H V ALARM

 

VLV ALARM

NO\NC

 

INPUT

DC GOOD

USER ALM

MAJOR

1

 

 

MINOR

8

LOW V

MAJ/MIN

SELECTVLV

OFFON

E101 +BAT

E102 -BAT

R101 V ADJ

Figure 5.4-1 MX06-100 Controller Layout

MX06-100 Rectifier Configuration

The system Controller Board must know if a rectifier is present for each of the five slots. This is done by the properly setting the dipswitch S2 (“RECT PRESENT”) on the Controller Board. If a rectifier is not present in a given slot, the corresponding switch position must be set to the “ON” condition. The ON direction is labeled on the body of the dipswitch. Figure 5.4-1 locates switch S2 on the PC board.

MX06 Power Plant User’s Manual

Page 24