MX06 External Alarm Input Configuration

The MX06-50 and the MX06-100 alarm input circuitry is the same for both controllers. Refer to board layouts in the preceding sections to identify switch 1. The four User Input Alarms can be programmed for either a MAJOR or MINOR alarm upon activation and can be configured for either a Normally Open (NO) or a Normally Closed (NC) input contact from the alarm source. Set dipswitch S1 to program the User Input Alarms. Refer to Figure 5.2-1 for details. The factory settings reflect normally open inputs (closed for alarm) with a MAJOR alarm priority for each user alarm.

Alarm

NO Setting

NC Setting

Major

Minor

Factory

Setting

Setting

Setting

 

 

 

User 1

S1-1 Open

S1-1 Closed

S1-5 Open

S1-5 Closed

NO/Major

User 2

S1-2 Open

S1-2 Closed

S1-6 Open

S1-6 Closed

NO/Major

User 3

S1-3 Open

S1-3 Closed

S1-7 Open

S1-7 Closed

NO/Major

User 4

S1-4 Open

S1-4 Closed

S1-8 Open

S1-8 Closed

NO/Major

Figure 5.2-1 User Alarm Settings

5.3. MX06-50 Configuration Settings

The control card for the MX06-50 is different than the control card for the MX06-100 due to increased number of rectifiers in the MX06-100. The control card for the MX06 is the 0P9172 and for the MX06-100, the control card is the 0P9745. This section will deal with configurations applicable to the MX06-50 only.

E13 E2

E4

E7

E9

R14

R30

R31

E8

E1

J2 J3 J5

S2

1

R4

R21

RECT PRESENT

NO/NC INPUT

S1

MAJ /MIN

SELECT

USER ALARMS

+BAT -BAT

R56

 

J4

V Adj

 

E3

 

E11

 

E12

 

E10

Figure 5.3-1 MX06-50 Controller Layout

MX06 Power Plant User’s Manual

Page 22

Page 26
Image 26
American Power Conversion MX06 50, MX06 100 MX06-50 Configuration Settings, MX06 External Alarm Input Configuration