MX06 100 Power System

Nominal Input Voltage

90, 115, 208, 230 VAC

 

 

 

Input Voltage Range

85

– 264 VAC

 

 

 

AC Frequency Range

47

– 63 Hz

 

 

Apparent Power Factor

99% Typical, 98% Minimum

 

 

 

Input Current

55

Amps @ 115 Volts AC

 

37 Amps @ 230 Volts AC

 

 

 

6.2. DC Output

TWF0500H5401 Rectifier

Output Voltage (factory set)

54.5 VDC

 

 

Operating Voltage Range

44 – 58 VDC

 

 

Efficiency

85% Typical

 

 

Over Voltage Protection

59.5VoltsDC

 

 

Output Current per

9.0 Amps Minimum Continuous at 115 VAC Input

Rectifier

10.5 Amps Minimum Continuous at 230 VAC Input.

 

 

Current Limit

9.3 Amps Maximum at 115 VAC Input

 

11.0 Amps Maximum at 230 VAC Input.

 

 

Power Output per Rectifier

490 W Continuous at 115 VAC Input

@ 54.5VoltsDC

570 W Continuous at 230 VAC Input

 

 

MX06 Power Plant User’s Manual

Page 27

Page 31
Image 31
American Power Conversion MX06 50 user manual DC Output, MX06 100 Power System