MX06-50 Rectifier Configuration

The system Controller Board must know if a rectifier is present for each of the five slots. This is done by the properly setting the dipswitch S2 (“RECT PRESENT”) on the Controller Board. If a rectifier is not present in a given slot, the corresponding switch position must be set to the “ON” condition. The ON direction is labeled on the body of the dipswitch. Figure 5.3-1 locates switch S2 on the PC board.

Figure 14 shows one style of dipswitch that may be on the board. On some controller boards, dipswitch S2 may consist of 10 small switches (instead of 5 large switches). In that case the switches must be used in pairs. I.E., for rectifier 1, the top 2 are a pair, for rectifier 5, the bottom 2 are a pair, and likewise for the middle switches.

MX06-50 Programmable Alarms

The GMT alarm, battery circuit breaker alarm and the AC / Input Healthy alarm can each be programmed to either MAJOR or MINOR alarm priority. A three-pin jumper header is used for each alarm in the manner shown in Figure 5.3-2. Figure 5.3-1 locates the jumpers on the PC board. If no jumper is in place, then no alarm will be reported.

1

2

3

 

1

2

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAJOR

 

MINOR

 

 

 

Figure 5.3-2 MX06-50 Jumper Programming.

 

 

 

 

 

 

 

 

Alarm

 

Jumper

Major

Minor

No Alarm

Factory

 

Designator

Setting

Setting

Output

Setting

 

 

GMT

 

J5

Pins

Pins

No

Major

Alarm

 

2 and 3

1 and 2

Jumper

 

 

 

Battery

 

 

Pins

Pins

No

 

Breaker

 

J3

Major

 

2 and 3

1 and 2

Jumper

Alarm

 

 

 

 

 

 

 

 

 

AC / Input

 

J2

Pins 2

Pins

No

No Alarm

Healthy

 

and 3

1 and 2

Jumper

 

 

 

Figure 5.3-3 MX06-50 Alarm Jumpers

MX06 Power Plant User’s Manual

Page 23

Page 27
Image 27
American Power Conversion MX06 100, MX06 50 MX06-50 Rectifier Configuration, MX06-50 Programmable Alarms, Setting Output