6.3. Controls and Indicators

TWF0500H5401 Rectifier

FAIL LED

DC output voltage below (-) 39.5 Volts DC or above (-) 59.5 Volts DC.

MX06 Controller

Voltage Good LED (Green)

On when voltage is between 50 and 57 Volts.

 

 

Major (Red)

On when Major Relay is energized

 

 

Minor (Yellow)

On when Minor Relay is energized

 

 

Low V LED 1 (Yellow)

On when voltage is below 50 Volts DC.

 

 

Very Low V LED (Red)

On when voltage is below 44 Volts DC.

 

 

6.4. Mechanical

TWF0500H5401 Rectifier

Dimensions

5 in (12.7 cm) high x 2-3/4 in (7cm) wide x 10.5 in (26.7 cm

 

deep

 

 

Weight

4 lbs (1.8 Kg)

 

 

Color

Grey Front, Yellow zinc sides and back

 

 

Mounting

Hot Swappable

 

 

MX06 Power Plant User’s Manual