Ventilation

The rectifier modules for this system have fans that provide front-to-rear airflow for internal cooling. The power system housing should be mounted such that there is free airflow to the front and back of the unit. [Refer to Section 6.5 for environmental characteristics.] Free airflow should be ensured so that the power system can provide full power at a given ambient temperature without de-rating.

3.3. AC Power Connections

WARNING: Ensure that all of the external DC and AC circuit breakers are in the OFF position prior to connecting service to the power plant. Confirm that all voltages have been removed including any battery sources before proceeding. Keep the rear cover in place when the system is operational or energized.

The DC power system requires the supply of 90/115/208/220/240 VAC single-phase, 50/60 Hz power. One AC input on the power system backplane supplies power to the first rectifier in each shelf. Two inputs supply power to the second and third pair of rectifiers and the fourth and fifth pair in each shelf. This scheme allows a variety of wiring options. Provided the input wiring is not overloaded, one, two or all three inputs on each shelf can be jumpered together. The ambient temperature and number of wires in a conduit must be considered in accordance with all applicable regulatory agencies.

Various AC input cable kits are available from APC. These cables are 12 feet (3.7m) long and have a power plug installed on each cable. When ordered with the power system, these cables will be installed with strain reliefs provided to mount the 3-conductor jacketed cables. Each kit will supply power to the entire power system. Use the chart in Figure 3.3-1 to determine the suggested cable kits.

Part Num.

AWG

Cable Qty

Plug Num.

Plug Style

Voltage

Power System

0M-91156

12

2

NEMA 5-20P

Non-locking

115

Magnum VS 50

0M-91154

12

2

NEMA L5-20P

Locking

115

Magnum VS 50

0M-91158

10

1

NEMA 5-50P

Non-locking

115

Magnum VS 50

0M-1150

12

2

NEMA L6-20P

Locking

230

Magnum VS 50

0M-91160

10

1

NEMA 6-30P

Non-locking

230

Magnum VS 50

0M-91159

10

1

NEMA L6-30P

Locking

230

Magnum VS 50

0M-91137

12

4

NEMA 5-20P

Non-locking

115

Magnum VS 100

0M-91141

12

4

NEMA L5-20P

Locking

115

Magnum VS 100

0M-91138

10

2

NEMA 5-50P

Non-locking

115

Magnum VS 100

0M-1149

12

4

NEMA L6-20P

Locking

230

Magnum VS 100

0M-91135

10

2

NEMA 6-30P

Non-locking

230

Magnum VS 100

0M-91136

10

2

NEMA L6-30P

Locking

230

Magnum VS 100

Figure 3.3-1 AC Input Wiring Kits