MX06 50 Power System

Output Voltage (factory

54.0

VDC

programmed)

 

 

 

 

Operating Voltage Range

47 – 57 VDC

 

 

 

Rated Output Current

52.5

A

 

 

Efficiency

85% Typical

 

 

 

Over Voltage Protection

59.5

Volts DC

 

 

Output Current

45 Amps Minimum Continuous at 115 VAC Input

 

52.5

Amps Minimum Continuous at 230 VAC Input.

 

 

 

Current Limit

46.5

Amps Maximum at 115 VAC Input

 

55.0

Amps Maximum at 230 VAC Input.

 

 

Power Output @ 54.5 VDC

2450 W Continuous at 115 VAC Input

 

2850 W Continuous at 230 VAC Input

 

 

 

MX06 100 Power System

 

 

 

 

 

Output Voltage (factory

54.0

VDC

programmed)

 

 

 

 

Operating Voltage Range

47 – 57 VDC

 

 

 

Rated Output Current

10.5

A

 

 

Efficiency

91% Typical

 

 

 

Over Voltage Protection

59.5

Volts DC

 

 

Output Current per

90 Amps Minimum Continuous at 115 VAC Input

Rectifier

105 Amps Minimum Continuous at 230 VAC Input.

 

 

Current Limit

93 Amps Maximum at 115 VAC Input

 

110 Amps Maximum at 230 VAC Input.

 

 

Power Output per Rectifier

4900 W Continuous at 115 VAC Input

@ 54.5VoltsDC

5700 W Continuous at 230 VAC Input

 

 

 