American Water Heater AHCG/HCG3 60T 120 - AHCG3/HCG3 100T 250 Vertical Termination Direct Vent

Models: AHCG/HCG3 60T 120 - AHCG3/HCG3 100T 250 Commercial Gas Water Heaters

1 80
Download 80 pages 24.27 Kb
Page 28
Image 28

2” (5 cm)

MAXIMUM

FIELD

SUPPLIED 90° ELBOW

FIELD SUPPLIED

PLUMBING

ROOF BOOT

OR FLASHING

FACTORY SUPPLIED

STANDARD TERMINATION POINTED DOWN TOWARDS THE GROUND

NOTE: INTAKE AIR

TERMINATION

SHOWN HERE

 

24 INCHES (61 cm) MINIMUM

48 INCHES (122 cm) IN COLDER CLIMATES

FIELD

INTAKE AIR

SUPPLIED

TERMINATION

90° ELBOW

 

VENT (EXHAUST)

 

TERMINATION

 

FACTORY SUPPLIED

MAINTAIN 12” (30 cm)

STANDARD TERMINATIONS

18” (45 cm) FOR CANADA

POINTED DOWNWARD

MINIMUM CLEARANCE

 

ABOVE HIGHEST

 

ANTICIPATED SNOW LEVEL.

MAINTAIN 12” (30 cm) 18” (45 cm) FOR CANADA MINIMUM CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL.

FIELD

SUPPLIED

STRAP/SUPPORT

VERTICAL TERMINATION(S) INSTALLATION

INTAKE AIR AND/OR VENT (EXHAUST)

Figure 23

FIELD SUPPLIED

PLUMBING

ROOF BOOTS

OR FLASHINGS

VERTICAL TERMINATION - DIRECT VENT

STANDARD TERMINATIONS

Figure 25

IF LESS THAN

10 FEET (3 m)

24 INCHES (60 cm)

MINIMUM HEIGHT ABOVE

INTAKE AIR AND/OR VENT TERMINATION(S) MUST BE A MINIMUM OF 24 INCES (60 cm)

ABOVE ANY PARAPET, VERTICAL WALL OR STRUCTURE WITHIN 10 FEET (3 m) HORIZONTALLY.

NOTE: VENT TERMINATION SHOWN HERE

VERTICAL TERMINATION(S) FLAT ROOF CLEARANCE

INTAKE AIR AND/OR VENT (EXHAUST)

Figure 24

28

Page 28
Image 28
American Water Heater AHCG/HCG3 60T 120 - AHCG3/HCG3 100T 250 instruction manual Vertical Termination Direct Vent