Start-up

System start-up

Single-UPS unit or redundant parallel UPS or UPS in "ECO" mode

See figure 20.

Proceed in the following order:

close the upstream switches supplying normal and bypass AC source power (on the LV switchboard);

close normal AC input switch Q1. The system powers up:

the rectifier/charger automatically starts,

green light 1 on the control panel goes on,

light 2 turns red;

close bypass AC input switch Q4S:

green lights 3 and 5 on the control panel go on;

close inverter output switch Q5N;

close battery circuit breaker QF1;

light 2 goes off;

open maintenance bypass switch Q3BP;

press the "inverter on" button 8 on the control panel:

the green "inverter" light 4 flashes,

the inverter starts, then, if the bypass AC source transfer conditions are satisfied, the load is transferred to the inverter if the on-line mode is selected, or the load remains on the static bypass if the "ECO" mode is selected,

the green "static-bypass" light 3 goes off,

the green "inverter" light 4 shines for on-line mode or flashes for "ECO" mode.

 

 

Q1

Q4S

Q3BP

Q5N

1

0

1

0

1

0

1

0

1

 

 

 

 

2

0

1

0

1

0

1

0

1

 

 

 

 

3

0

1

0

1

0

1

0

1

 

 

 

 

QF1

4

 

0

I

5

0

1

0

1

0

1

0

1

 

 

 

 

6

20 - 200 kVA

Fig. 20

Parallel UPS unit for increased output

See figure 21.

Proceed in the following order:

check that all load devices are off or that the load is disconnected;

close the upstream switch supplying normal AC source power (on the LV switchboard);

close the normal AC input switches Q1 on the UPS units. The system powers up:

the rectifier/chargers automatically start,

the green "rectifier/charger" lights 1 in the control panels go on,

lights 2 turn red;

close the battery circuit breakers QF1;

lights 2 go off;

close Mains 2 input switch Q4S in the external bypass unit:

green lights 3 and 5 on the control panels go on;

close output switches Q5N for the inverters and in the external bypass unit;

open maintenance bypass switch Q3BP in the external bypass unit;

press the "inverter on" button 8 on each control panel:

the green "inverter" lights 4 flash;

when a sufficient number of inverters are ready, the inverter-output contactors close:

the green "inverter" lights 4 shine permanently green;

the "static-bypass" lights 3 go off.

 

 

Q1

Q5N

1

0

1

0

1

 

 

QF1

2

 

I

 

Q1

0

Q5N

3

0

1

0

1

 

 

4

20 - 200 kVA

Fig. 21

Single-converter unit or redundant parallel converter unit

See figure 21.

Proceed in the following order:

close the upstream switch supplying normal AC source power (on the LV switchboard);

close normal AC input switch Q1. The system powers up:

the rectifier/charger automatically starts,

green light 1 on the control panel goes on;

close battery circuit breaker QF1;

close inverter output switch Q5N;

press the "inverter on" button 8 on the control panel:

the green "inverter" light 4 flashes,

the inverter starts up, then connects. The load is then supplied by the inverter,

the green light 4 shines permanently, and light 5 turns green.

Note:

Each time a device is switched on, a lamp test is run: all the lights turn orange for roughly 1 second. The message "autotest OK" is displayed until the first primary message is sent.