E-51028230XT/BG - 19

Shutdown of a rectifier/

charger

Except in frequency converters without
a battery, it is recommended not to stop
the rectifier/charger because the
battery will no longer be charged.
Except in the case of a test of the
inverter on battery power, the rectifier/
charger should be shutdown after the
inverter to avoid unnecessary battery
discharge.
Proceed in the following order:
open battery circuit breaker QF1;
open normal AC input switch Q1:
the rectifier/charger shuts down,
the green "rectifier/charger" light 1
goes off.
Note:
In a frequency converter without a
battery, rectifier/charger shutdown
automatically results in inverter
shutdown.

Shutdown of the

inverter

press the "inverter OFF" button 9 on
the control panel for three seconds (see
figure 19).

Single-UPS unit

the green "inverter" light 4 on the
control panel goes off;
the green "static-bypass" light 3
goes on;
the inverter stops;
if bypass AC source (Mains 2)
transfer conditions are satisfied, the
inverter shuts down and the load is
transferred to the bypass AC source;
if bypass AC source (Mains 2)
transfer conditions are not satisfied, the
inverter does not shut down. The
message "MAINS 2 OUTSIDE
TOLERANCES, TRANSFER
DISABLED" is displayed.

UPS in "ECO" mode

the green "inverter" light 4 on the
control panel goes off;
if the load was on the static bypass,
nothing is changed;
if the load was on the inverter:
the green "static-bypass" light 3
goes on,
if bypass AC source (Mains 2)
transfer conditions are satisfied, the
inverter shuts down and the load is
transferred to the bypass AC source,
if bypass AC source (Mains 2)
transfer conditions are not satisfied, the
inverter does not shut down. The
message " MAINS 2 OUTSIDE
TOLERANCES, TRANSFER
DISABLED" is displayed.
Shutdown

Single-converter unit

the green lights 4 and 5 on the
control panel go off;
the inverter stops.

Parallel UPS unit

if the system is redundant, i.e. the
other parallel-connected inverters can
supply the load on their own, the
inverter shuts down and the green
"inverter" light 4 goes off.
The load is not affected in that the other
inverters continue to supply it normally;
if the system is not redundant, the
other inverters go to overload status.
If overload conditions are overrun, the
load is transferred to the bypass AC
source:
the green lights 3 turn green,
the green "inverter" light 4 goes off.

Parallel-converter unit

the redundant system means that the
other parallel inverters can supply the
load unassisted. The inverter shuts
down and the green "inverter" light 4
goes off. The load is not affected in that
the other inverters continue to supply it
normally;