Shutdown

Shutdown of the inverter

press the "inverter OFF" button 9 on the control panel for three seconds (see figure 19).

Single-UPS unit

the green "inverter" light 4 on the control panel goes off;

the green "static-bypass" light 3 goes on;

the inverter stops;

if bypass AC source (Mains 2) transfer conditions are satisfied, the inverter shuts down and the load is transferred to the bypass AC source;

if bypass AC source (Mains 2) transfer conditions are not satisfied, the inverter does not shut down. The message "MAINS 2 OUTSIDE TOLERANCES, TRANSFER DISABLED" is displayed.

UPS in "ECO" mode

the green "inverter" light 4 on the control panel goes off;

if the load was on the static bypass, nothing is changed;

if the load was on the inverter:

the green "static-bypass" light 3 goes on,

if bypass AC source (Mains 2) transfer conditions are satisfied, the inverter shuts down and the load is transferred to the bypass AC source,

if bypass AC source (Mains 2) transfer conditions are not satisfied, the inverter does not shut down. The message " MAINS 2 OUTSIDE TOLERANCES, TRANSFER DISABLED" is displayed.

Single-converter unit

the green lights 4 and 5 on the control panel go off;

the inverter stops.

Parallel UPS unit

if the system is redundant, i.e. the other parallel-connected inverters can supply the load on their own, the inverter shuts down and the green "inverter" light 4 goes off.

The load is not affected in that the other inverters continue to supply it normally;

if the system is not redundant, the other inverters go to overload status. If overload conditions are overrun, the load is transferred to the bypass AC source:

the green lights 3 turn green,

the green "inverter" light 4 goes off.

Parallel-converter unit

the redundant system means that the other parallel inverters can supply the load unassisted. The inverter shuts down and the green "inverter" light 4 goes off. The load is not affected in that the other inverters continue to supply it normally;

Shutdown of a rectifier/ charger

Except in frequency converters without a battery, it is recommended not to stop the rectifier/charger because the battery will no longer be charged. Except in the case of a test of the inverter on battery power, the rectifier/ charger should be shutdown after the inverter to avoid unnecessary battery discharge.

Proceed in the following order:

open battery circuit breaker QF1;

open normal AC input switch Q1:

the rectifier/charger shuts down,

the green "rectifier/charger" light 1 goes off.

Note:

In a frequency converter without a battery, rectifier/charger shutdown automatically results in inverter shutdown.

E-51028230XT/BG - 19

Page 19
Image 19
APC 20 - 200 KVA user manual Shutdown of the inverter, Shutdown of a rectifier/ charger, UPS in ECO mode