E-51028230XT/BG - 5
Introduction

General characteristics of MGE™ Galaxy™ PW UPSs

UPS power rating in kVA 20 30 40 50 60 80 100 120 160 200
Normal AC input
number of conductors 3 phases
rated voltage and tolerances 380 V or 400 V or 415 V ± 10% (adjustable to ± 15%)
rated frequency and tolerances 50 Hz or 60 Hz / ± 10%
THDI with THM filter < 4%
power factor with THM filter up to 0,96
Bypass AC input
number of conductors 3 phases + neutral
rated voltage and tolerances 380 V or 400 V or 415 V / ± 10%
rated frequency and tolerances 50 Hz or 60 Hz / ± 10%
Load
number of conductors 3 phases + neutral
Ph/Ph voltages 380 V or 400 V or 415 V (according to setting)
Ph/N voltages 220 V or 230 V or 240 V (according to setting)
voltage fluctuations ± 0,5%
adjustable frequency and tolerances
(on battery power) 50 Hz or 60 Hz ± 0,05 Hz
synchronisation with bypass ± 0,5 Hz (adjustable from ± 0,25 Hz to ± 2 Hz)
voltage variation for 0 to 100% load step change ± 2% ((with battery)
permissible overloads 150% for 1 minute, 125% for 10 minutes
Isc Ph/Ph (% of I rated) 4.2 2.8 2.1 2.5 2.1 3.1 2.5 2.1 2.6 2.1
Isc Ph/N (% of I rated) 6.6 4.4 3.3 4 3.3 5 4 3.3 4 3.3
THDU Ph/Ph and Ph/N for linear load < 1,5% Ph/Ph, < 2% Ph/N
THDU Ph/Ph and Ph/N for non-linear load < 2% Ph/Ph, < 3% Ph/N
(at 80% of Pn) (1)
Battery
standard battery type gas-recombination sealed lead-acid battery
UPS characteristics
active power (kW) 16 24 32 40 48 64 80 96 128 160
efficiency at 50% load (%) 87.5 90.5 91.5 92.5 93 91 91.5 92 93 93.2
(values ± 1%)
efficiency at 100% load (%) 91.5 92 91.5 93 92 92.5 92 91.5 92.8 92.5
(values ± 1%)
heat losses (2) in KW 1.5 2.1 3.4 3.6 4.7 6.2 8.1 10.1 12.2 14.8
in cal./s 360 504 816 864 984 1488 1950 2420 2930 3550
storage temperature range -25 °C to +70 °C
operating temperature range 0 °C to 35 °C (40 °C for 8 hours)
relative humidity 95% maximum
maximum operating altitude without derating < 1000 meters
noise level (dBA) 58 58 58 60 60 62 64 65 67 68
dimensions (mm) width 715 1015 1215
depth 825
height 1400 or 1900 ± 10 1900 ± 10
weight (kg) (3) 450 450 450 490 490 800 800 800 1200 1200
recommended upstream earth-fault protection 1 A
standards design IEC 146
product ENV 50091
safety IEC 950, ENV 50091
protection IEC 521 (cubicles 1400 mm high = IP 21, cubicles 1900 mm high = IP 20)
electromagnetic compatibility IEC 62040, ENV 50091
(1): As per standards ENV 50091-3 / IEC 62040-3.
(2): The losses indicated are those produced at full rated load with the battery float charging. They must be taken into account when sizing the ventilation system.
(3): Not including any built-in options, such as harmonic filters or a bypass AC-source isolation transformer.