Control-panel display (cont.)
Measurement system
The display 23 may be used to read a number of input and output measurements made at different points in the system. See, in the Appendix, figure 23.
◗normal AC source 1
◗
◗currents of the three phases,
◗frequency;
◗bypass AC source 2
◗
◗
◗frequency,
◗currents of the three phases;
◗battery 3
◗voltage;
◗charge or discharge current;
◗remaining battery time (for the UPS unit concerned);
◗battery temperature;
◗inverter output 4
◗frequency;
◗total load 6
◗
◗
◗currents of the three phases,
◗frequency,
◗active and apparent power.
Note:
Frequency converters without batteries are not concerned by the battery measurements. The displayed battery voltage corresponds to the DC voltage at the rectifier/charger output.
Bypass AC source 2 measurements are not displayed on frequency converters
1 | 3 | 4 | 6 |
U - I - F | U - I | F | U - V - I - F - P |
A |
| B |
|
Q1 |
|
| Q5N |
1 |
|
|
|
| QF1 |
|
|
2 |
| D |
|
|
|
| |
U - V - I - F |
| C |
|
Q4S |
|
|
|
2 |
|
|
|
Fig. 23
Voltage measurements
These measurements may be accessed by pressing the "V" key 14 . The following data is displayed.
Note:
M1: normal AC source
M2: bypass AC source
Current measurements
These measurements may be accessed by pressing the "A" key 15 . The following data is displayed.
Note:
CF: crest factor
Power and frequency measurements
These measurements may be accessed by pressing the "W.HZ" key 16 . The following data is displayed.
Note:
PF: power factor
RMS | M1 | M2 | LOAD | RMS | M2 | LOAD |
U12 | V1 | |||||
U23 | V2 | |||||
U31 | V3 | |||||
|
|
|
|
| ||
|
|
|
|
| ||
RMS | M1 | M2 | LOAD | |||
I1 | % | |||||
I2 | % | |||||
I3 | % | |||||
|
|
|
|
|
| |
|
|
|
|
|
| |
LOAD | KW | KVA | PL/PN | = | FREQ.HZ | |
P1 |
|
| M1 | |||
P2 |
|
| M2 | |||
P3 | FP.LOAD = | INV | ||||
|
|
|
|
|
|
|