Programming Parameters
NOTE:
The system must not run in bypass mode for extended periods of time as the batteries will not be charged.
4.0Programming Parameters
4.1General
Some operating parameters can be programmed directly from the keyboard. Unless you are quite sure of the consequence of changing the following parameters, please contact your local APC dealer for assistance.
Parameters are programmed as shown in the example 4.2.3.
4.2 | Parameters |
|
|
|
|
|
|
4.2.1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Parameter | Setting* | Comments |
|
|
|
| |
Bypass | YES, NO | “YES” will switch the system into | |||||
|
|
| bypass mode |
|
|
|
|
Language | GB, D, F, I, | Language of text in display | |||||
|
| DK, S, SF, |
|
|
|
|
|
|
| NL, PL, CZ, |
|
|
|
|
|
|
| E, P, SK, H |
|
|
|
|
|
|
|
|
|
| |||
Autostart | YES, NO | Automatic restart of UPS upon utility return. | |||||
|
|
| Ensures quick battery recharge. | ||||
|
|
|
|
| |||
Remote shutdown | YES, NO | Shutdown of UPS by remote signal | |||||
active |
|
|
|
|
|
|
|
|
|
|
|
| |||
Remote shutdown | HIGH, LOW | Nature of remote shutdown signal polarity | |||||
polarity |
|
|
|
|
|
| |
|
|
|
|
| |||
Remote shutdown time | 0, 1, 2, 3, 4 | Time delay on remote shutdown of UPS | |||||
|
| 5, 6, 7, 8, 9 |
|
|
|
|
|
|
| 10 min. |
|
|
|
|
|
Battery capacity test | - | Initiates check of | |||||
|
|
| measured time is from start until it reaches | ||||
|
|
| low DC warning level (See section 8.4) | ||||
|
|
|
|
| |||
Battery monitor test** | - | Initiates check of battery condition by | |||||
|
|
| 25% discharging. |
| |||
Automatic battery test** | NO, 3, 6 | Activates the battery monitor test in cyclic | |||||
|
|
| intervals (Unit - months) |
| |||
Battery monitor reset** | - | Pressing the | and |
|
| key after | |
| |||||||
|
|
| selecting this parameter resets any battery | ||||
|
|
| alarms. |
|
|
|
|
|
|
| |||||
Boost charge | YES, NO | “YES” results in boost charge (10 hours) | |||||
|
|
| |||||
Autoboost charge | YES, NO | “YES” results in boost charge after every | |||||
|
|
| battery operation (10 hours) | ||||
|
|
| |||||
Enter new date | YYMMDD | Local date can be entered | |||||
Enter new time | HHMMSS | Local time can be entered (24 hour clock) | |||||
|
|
|
|
|
|
|
|
*Text in bold letters are the standard setting
**Only for systems with battery monitor active
7OA0002 US rev. 04
16 | User Guide Silcon DP300E Series 480V |