APC DP300E manual Start from complete power down, Starting up Silcon DP3240E DP3320E

Models: DP300E

1 38
Download 38 pages 1.86 Kb
Page 7
Image 7

Stop, Start & Operating the External Service Bypass Panel

WARNING:

Make sure that all cable con– nections are in place prior to starting-up the first time after having completed the electrical installation.

NOTE:

After starting-up the system first time, check that the battery temperature can be displayed. (Press 5 and 8 simultaneously on the display; if not correctly installed display will show NV (Not Valid)). It is recommended to perform a battery capacity test after having completed the installation.

2.5Start (from complete power down)

2.5.1Starting up Silcon DP3240E – DP3320E

1.Ensure that the system has been at stable environment for at least 12 hours to ensure any condensation has been evaporated before starting up.

NOTE:

If the start up procedure for any reason is interrupted – wait until the display shows the step 4 picture and repeat from this step.

WARNING:

Do not close the external battery MCCB’s without the display showing “Close MCCB”

otherwise you may damage the UPS.

If the display shows: “DC capacitor charge error”, do not close MCCB, but call for assistance.

WARNING:

If “Autostart” is active (please refer to 4.2.1) the UPS will start automatically after step 9 with a delay of 1 minute.

2.Prepare the system by opening the front door(s).

3.Switch on the utility power supply

4.Wait about 10 seconds

5.Press on the keyboard

6.Press on the keyboard

7.Wait about 1 second

8.Wait about 1 minute

9.Close battery MCCB’s in MCCB-box or battery cubicle.

Please refer to LED indication and labelling in MCCB-box or battery cubicle.

10.Press the green “ON“ push-button.

11.Close the front door.

Display shows

System type XXX

XXX kVA - XXX

Stop charge DC capacitors : YES

Start charge DC capacitors : YES

Data stored

Start charge DC capacitors : YES

Insert fuse or

close MCB

** System OFF **

Normal operation load power XX%

Start up of system now completed.

7OA0002 US rev. 04

User Guide Silcon DP300E Series 480V 240-320kVA

7

Page 7
Image 7
APC DP300E manual Start from complete power down, Starting up Silcon DP3240E DP3320E