Programming Parameters

NOTE:

Only for APC personnel and certified local APC personnel.

4.4Programming of battery monitor

Action

 

 

Display shows

1. Press

and

simultaneously to open

Key in password

 

 

for password input

:

 

 

 

2.Enter password xx xx xx by pressing

Last selected

parameter

3. Press

or

until

Expected back-up

time [min.]: XXX.X

 

 

 

4.Enter the expected back-up time in min. at 100% ohmic (pf = 1) load, when the inverter has a mean efficiency of approx. 96%

Press I.e. 14.0 min.

5.Press to store data

6. Press or until

7 Press

to set Ah for battery

8.Press to store data

9.Press to exit

Expected back-up

time [min.]: 14.0

Data stored

Battery capacity

in [Ah]: XX.X

Battery capacity

in [Ah]: 7.0

Data stored

Normal operation load power XX%

Installation of new batteries:

When installing new batteries the procedure in section 4.4 MUST be carried out, otherwise the monitor may give false alarms.

7OA0002 US rev. 04

20

User Guide Silcon DP300E Series 480V 240-320kVA

Page 20
Image 20
APC DP300E manual Programming of battery monitor, Installation of new batteries