Remote Display
NOTE:
The alarm can be reset from
remote display.
7.0Remote Display
7.1Remote Display Operation
The remote display is an inactive unit that is unable to influence the operation of the Silcon DP300E. It is impossible to adjust or influence the function of the DP300E. The alarms available on remote display are a subset of the alarms, which can be shown on the internal display. Available alarms are described in section
7.3.6.
7.1.1Starting up the remote display
After having connected the supply the display will show:
“Remote display: DP300E UPS”
7.1.2Setting remote display
Through the
Parameter | Setting | Comments |
Language | GB, D, F, DK, S, SF, NL, | Language of text in |
| PL, CZ, E, P, SK, H | display |
|
|
|
Host | SDC charger, DP300E, | The type of UPS to which |
|
| the remote display has |
|
| been connected |
|
|
|
7.1.3Operation
As described in section 3.0 Operation.
7.1.4Reading out measurements
As described in section 5.0 Reading out measurements. However, reading out of time and utility 2 current is not possible from remote display.
7.1.5Alarms
It is possible to show the following alarms:
Possible alarm | Description |
|
|
Output is out of tolerance | Output voltage outside limits |
|
|
Battery voltage low, shutdown | The battery has been discharged to |
| minimum permissible level |
|
|
Common fault | An alarm is detected by the UPS |
|
|
Overload. Load is over 100% | Overload on UPS |
|
|
High temperature static switch | Temperature on input or bypass static |
| switch to high |
Synchronization error | The UPS cannot synchronize to the input |
| frequency |
|
|
Datatransmission interrupted | A fault in the communication between UPS |
| and remote display |
|
|