Remote Display

NOTE:

The alarm can be reset from

remote display.

7.0Remote Display

7.1Remote Display Operation

The remote display is an inactive unit that is unable to influence the operation of the Silcon DP300E. It is impossible to adjust or influence the function of the DP300E. The alarms available on remote display are a subset of the alarms, which can be shown on the internal display. Available alarms are described in section

7.3.6.

7.1.1Starting up the remote display

After having connected the supply the display will show:

“Remote display: DP300E UPS”

7.1.2Setting remote display

Through the #-stack it is possible to set language and to which type of UPS the remote display has been connected.

Parameter

Setting

Comments

Language

GB, D, F, DK, S, SF, NL,

Language of text in

 

PL, CZ, E, P, SK, H

display

 

 

 

Host

SDC charger, DP300E,

The type of UPS to which

 

 

the remote display has

 

 

been connected

 

 

 

7.1.3Operation

As described in section 3.0 Operation.

7.1.4Reading out measurements

As described in section 5.0 Reading out measurements. However, reading out of time and utility 2 current is not possible from remote display.

7.1.5Alarms

It is possible to show the following alarms:

Possible alarm

Description

 

 

Output is out of tolerance

Output voltage outside limits

 

 

Battery voltage low, shutdown

The battery has been discharged to

 

minimum permissible level

 

 

Common fault

An alarm is detected by the UPS

 

 

Overload. Load is over 100%

Overload on UPS

 

 

High temperature static switch

Temperature on input or bypass static

 

switch to high

Synchronization error

The UPS cannot synchronize to the input

 

frequency

 

 

Datatransmission interrupted

A fault in the communication between UPS

 

and remote display

 

 

7OA0002 US rev. 04

30

User Guide Silcon DP300E Series 480V 240-320kVA