19User Guide Silcon DP300E Series 480V 240-320kVA
7OA0002 US rev. 04
Programming Parameters
4.3.2 Programming example – change charge voltage to 446V*
Action Display shows
1. Press and simultaneously to open
for password input
2. Enter password xx xx xx by pressing
3. Press or until
4. Press
5. Press to store
6. Wait about 1 second
7. Press to exit
4.3.3 Programming example - change to output isolation transformer
present**
Action Display shows
1. Press and simultaneously to open
for password input
2. Enter password xx xx xx by pressing
3. Press or until
4. Press for change
5. Press to store
6. Wait about 1 second
7. Press to exit
Last selected
parameter
Boost charge voltage
: 438
Boost charge voltage
: 446
Data stored
Boost charge voltage
: 446
Normal operation
load power XX%
Key in password
:
Key in password
:
Last selected
parameter
Normal operation
load power XX%
Isolation trafo output
: YES
Data stored
Isolation trafo output
: NO
Isolation trafo output
: YES
** The other parameters are
selected by pressing the key
as step 4 in example 4.3.3. -
one or more times.
NOTE:
Only for APC personnel and
certified local APC personnel.
* For charge voltages, battery
warnings and shut down
voltages, and high battery
temperature, the parameter is
changed by entering the actual
value like example 4.3.2.