Alarms
6.6Possible alarms
| Possible alarm | Description | Action | |
|
|
|
|
|
| 1. | Peak current limiter active | Peak current limiter has | Check for blown |
|
|
| been activated and UPS | fuses in your |
|
|
| switched to bypass opera- | installation |
|
|
| tion. System overloaded |
|
|
|
|
|
|
| 2. | Bypass power supply fault | Fault in redundant PSU | Call for assistance |
|
|
| for bypass. UPS has still |
|
|
|
| 100% performance and can |
|
|
|
| operate in all modes |
|
| 3. | Delta current limiter active | Input current limiter has | Check for overload. |
|
|
| been activated and UPS | If repetitiv – call for |
|
|
| switched to bypass opera- | assistence |
|
|
| tion |
|
| 4. | Fan fault | Blocked or faulty fan | Remove blocking or |
|
|
|
| call for assistance |
|
|
|
|
|
| 5. | High DC warning | Switching off big output load | If repetitive reduce the |
|
|
|
| load change |
| 6. | High DC shutdown | Fault in UPS | Call for assistance |
| 7. | Off button pushed | Off button or emergency | – |
|
|
| power down activated |
|
| 8. | Synchronization error | The UPS can’t synchronize | Check if phase |
|
|
| to the input frequency | rotation of main input |
|
|
|
| voltage is correct – if |
|
|
|
| OK call for assistance |
| 9. | Inverter voltage error | Inverter average voltage out | – |
|
|
| of limits (normal message |
|
|
|
| during starting up/switching |
|
|
|
| off the system) |
|
| 10. | Parallel sync. error | Parallel UPS’s are not able | Check external |
|
|
| to synchronize | parallel cables |
|
|
|
| Call for assistance |
| 11. | Inverter current limiter | Overload on inverter | Reduce UPS output |
|
| active |
| load |
| 12. | Overload Load is over | Overload on UPS | Reduce UPS output |
|
| 100% |
| load |
| 13. | Second power supply fault | Fault in UPS | Call for assistance |
|
|
| (Only in systems >160kW) |
|
| 14. | Internal power supply fault | Fault in UPS. Only bypass | Call for assistance |
|
|
| operation possible |
|
| 15. | Battery MCB is off | Battery MCCB switch not | Close MCCB. |
|
|
| closed or released. | If released again |
|
|
|
| – call for assistance |
| 16. | ** Q004 off ** | Position of output switch for | – |
|
|
| UPS in parallel |
|
| 17. | ** Q003 on ** | Position of external bypass | – |
|
|
| switch |
|
| 18. | ** Q002 off ** | Position of UPS output | – |
|
|
| switch |
|
| 19. | ** Q001 or Q010 off ** | Position of UPS input switch | – |
|
|
|
|
|
|
|
|