Stop, Start & Operating the External Service Bypass Panel

Single Utility

Dual Utility

2.6Operating the external service bypass switch, single systems

2.6.1Bypassing the UPS

Action

 

 

Display shows

1.

Press

on the keyboard

 

2.

Press

or

on the keyboard until

Bypass operation

: NO

 

 

 

 

3.

Press

on the keyboard

Bypass operation

: YES

 

 

 

 

4.

Press

on the keyboard

 

Lamp indication on bypass panel

WARNING!

If the UPS is out of service for more than 48 hours the connected batteries might be damaged. Refer to total “Switching off“ as described in

5.Check lamp indication on the bypass panel

6.Turn the external bypass switch (Q003) to position “1“.

7.Turn the output switch (Q002) to position “0“.

8.Open the front door and press the red “OFF“ push-button.

The acoustic alarm sounds for 30 secs.*

9.Turn the input switch (Q001) to position “0“. Turn the bypass input switch (Q010) to position “0”, if dual utility is present.

The red alarm LED below the display lights and the acoustic alarm sounds for 30 secs.

The green lamp (H003) above the bypass switch handle (Q003) lights

The green lamp (H002) above the output switch handle (Q002) lights

Only the lamp (H002) above the output switch handle (Q002) lights now

Display shows

**System OFF**

chapter 2.4.1.

7OA0002 US rev. 04

* The acoustic alarm can be reset by the key

EMERGENCY (UPS not alive)

1.Turn the bypass switch (Q003) to position “1“.

2.Turn the output switch (Q002) to position “0“.

3.Turn the input switch (Q001) to position “0“.

4.If dual utility is present, turn bypass input switch (Q010) to position “0”.

5.Change released system input fuse(s), if any.

8

User Guide Silcon DP300E Series 480V 240-320kVA