PROGRAMMING EXAMPLE

As an example of a programming sequence, the following values, gained from a temperature-time monitoring application, are programmed into the indicator.

DISPLAY: Display the actual temperature of a liquid solution in ￿F. Activate alarm #1 output when temperature falls below 25￿F, activate display alarm. Peak and valley (max/min) readings for each cycle to be recorded.

TOTALIZER: When total exceeds 30,000 degree-minutes then latch alarm #2 which stops the heating process and sounds a process complete bell. Reset alarm #2 by remote input. Disable totalization when temperature falls below 200￿F. Reset the total from the front panel. Allow switching of the display from/to temperature and total.

SERIAL: Provide hardcopy printout of total, input and peak/valley when operator actuates print request. Baud rate 300.

ANALOG RE-TRANSMISSION:Record temperature profile. 4 mA at 50￿F and 20 mA at 200￿F.

“Pro 1”

“tYPE”

-

Enter 400

 

“SCALE”

-

Enter F

 

“dECPNt”

-

Enter 0

“Pro 2”

“SLOPE”

-

Enter 1.0000

 

“OFFSEt”

-

Enter 0

“Pro 3”

“dSP AL”

-

Enter yes

 

“ENt AL”

-

Enter yes

 

“dSPHYS”

-

Enter no

 

“rSt AL”

-

Enter no

 

“dSPbUF”

-

Enter yes

 

“rStbUF”

-

Enter yes

 

“SELdSP”

-

Enter yes

 

“rSttOt”

-

Enter yes

 

“dSPOFF”

-

Enter no

“Pro 4”

“FILter”

-

Enter 1 (Normal)

 

“E1-CON”

- Enter 7 (reset alarm #2)

 

“E2-CON”

- Enter 14 (print request)

“Pro 5”

“tbASE”

-

Enter 1

 

“SCLFAC”

-

Enter 1.000

 

“Lo-cut”

-

Enter 200

“Pro 6”

“trAc”

-

Enter no

 

“dISP”

-

Enter yes

 

“LAtC-1”

-

Enter no

 

“ASN-1”

-

Enter input

 

“AL-1”

-

Enter 25

 

“HYS-1”

-

Enter 1

 

“Act-1”

-

Enter LO

 

“LAtC-2”

-

Enter yes

 

“ASN -2”

-

Enter total

 

“AL-2”

-

Enter 30000

 

“HYS-2” - N/A

 

“Act-2”

-

Enter HI

“Pro 7”

“bAud”

-

Enter 300

 

“AddrES”

-

Enter 0

 

“Print”

-

Enter 6

 

“FULL”

-

Enter yes

“Pro 8”

“ASIN”

-

Enter input

 

“AN-Lo”

-

Enter 50

 

“AN-HI”

-

Enter 200

-21-