S.F . = 110 x ( 3600￿￿) ￿ x 10

110 28800 10 (8 Hours x 3600)

S.F. = 1x.125

S.F. = .125

“Pro 5”.....“dECPNt” - 0.0

“tbASE ” - 2 “SCLFAC” - .125

“Lo-cut ” - 0.0

￿This value is normally 1, but can be used as a course scale factor of 60 or 3600.

￿￿Since the time period is in Hrs., the selected T.B. is 3600 (Program select value = 2) which equals per hour (3600 sec.).

The integrator/totalizer will accumulate up to 99999.9. At the end of the shift, the average temperature over the previous 8 hours can be read directly. The integrator/totalizer can then be reset for the next 8 hour shift. Anytime during the shift, the average temperature can be calculated by the following formula:

Av =

 

I.V.

 

S.F.

x T.T.￿￿￿

 

I.V. = Integrator/Totalizer Value

S.F. = Programmable Scale Factor

T.T. = Total Time (From the beginning of the shift)

For example, 6 hours and 37 minutes into the shift the integrator/ totalizer reads “90.9”. To find the average temperature up to this point:

Av =

90.9

=

90.9

Av = 109.9

 

.125 x 6.6166

.827

The average temperature over the last 6 hours and 37 minutes was 109.9°F.

￿￿￿Time is in hours. The number of minutes must be divided by 60 and then added to the hours.