ATON AH66T-KT Sense Input / Trigger Output, RS-232 /IR / A-NetControl, Symptom, Possible Cause

Models: AH66T-KT

1 90
Download 90 pages 12.31 Kb
Page 53
Image 53
Sense Input / Trigger Output

A T O N

AH66T INSTALLATION MANUAL

 

 

Sense Input / Trigger Output

Symptom

Possible Cause

Solution

 

 

 

 

 

Conditional power

1.

Conditional programming incorrect

1.

Verify/correct programming in the ATON configuration

command for

 

 

 

software

monitor not

2.

Sensor faulty or not connected

2.

Verify/correct Sensor operation and connection.

working properly

 

properly

 

 

 

 

 

 

 

3.

Incorrect Sensor being used

3.

Use correct sensor

 

 

 

 

 

System Trigger Out

1.

Faulty or incorrect 3.5mm cable

1.

Correct wiring – Use a MONO 3.5mm cable.

not working

 

being used.

 

 

properly

2.

Check for 12VDC with multi-meter

2.

100mA maximum current

 

 

 

 

 

 

RS-232 / IR / A-Net Control

Symptom

Possible Cause

Solution

 

 

 

 

 

Zone IR receive LED

1.

IR controller not programmed.

1.

Program IR controller or correct programming.

does NOT flash

 

 

 

 

when a button is

 

 

 

 

pressed.

2.

IR signal path wiring bad.

2.

Verify IR signal path wiring. Check touchpads, IR

 

 

 

 

 

sensors, AH66T IR Input jack, etc.

 

 

 

 

 

Intermittent control

 

IR flooding.

 

Zone IR receive LED glowing or flickering when no

from IR controller.

 

 

 

commands are being sent indicates IR flooding.

 

 

 

 

Possible sources: ambient light or plasma / LCD TV

 

 

 

 

flooding.

 

 

 

 

 

A-Net commands

1.

A-Net wiring incorrect.

1.

Verify wiring.

not working

2.

Chassis unit ID set incorrectly.

2.

Set chassis unit ID correctly. (See page 47)

 

 

3.

Incorrect commands

3.

Verify / Correct programming

 

 

 

 

 

3rd Party RS-232

1.

No connection from RS-232

1.

Connect RS-232 controller

commands not

 

controller to the AH66t

 

 

working

2.

Faulty connection / incorrect pin

2.

Correct wiring / Verify correct DB-9 to RJ45 adapter is

 

 

 

configuration

 

being used (DB9F-RJ45 NULL Modem)

 

3.

AH66T RS-232 configuration not

3.

Configure the correct settings using the ATON

 

 

correct for the RS-232 controller

 

configuration software

 

 

being used

 

 

 

 

 

 

 