9.Connect the tubing from the reference Gas regulator to Zone 1on the manifold of HGM300. NOTE: Fault light on HGM300 may illuminate until gas starts to flow from the reference bottle. Press the enter key from keyboard the sensor readings will update indicated by a beep sound from the HGM300. The pressure should be below the original readings, if not the unit is in a Purge cycle wait until purge cycle is complete then continue. Adjust the variable regulator clockwise to set the pressure to the original pressure reading from step 7 (press the enter key to update the readings). NOTE: You may have to block or partially block relief valve on variable pressure regulator in order to achieve desired pressure. Continue this until pressure readings are the same as original readings. Allow the gas to flow for 1 minute, continue to press the enter key while observing the first PPM reading (6th line) from the sensor data menu. This value will stabilize to (typically) within
9.Close reference bottle by adjusting variable regulator counter clockwise until fully closed. Return Zone 1 parameters (length, refrigerant, hold time) to desired operating values.
10.If the reading in step 8 is not within