Configuration using the PC |
Only Digital inputs can be used for this purpose. The selection shown in the list box is restricted to inputs that are set to digital in the Hardware section.
To use this feature, the input must be selected in the Points section and enabled.
Default Special Function Input: NONE.
3.5.4 Directories
The Directories contain the sequences of actions that will occur when an alarm is activated in a group. Instructions for dialing, speaking, inserting delays and signaling are placed in the directory in the order in which they are to be performed. Each of the six directories can contain unique operational sequences. The directory summary displays the sequence of events in a
The editor dialog box displays two columns on the left, one for the Command entry and the other for the Value entry, if any. Buttons for each type of command are arranged on the right. Commands are entered when you click on the buttons on the right side of the dialog box. The command appears at the location currently selected
The commands and their functions are:
Dial
The Dial command is the first command entry. Associated with the Dial command is a telephone number that is entered in the Value field; this is the number that will be called when an alarm condition is detected. The maximum length of the telephone number is 39 digits. The special character ‘!’ can be inserted anywhere in the telephone number to create a two second delay in the dialing sequence.
When this command is encountered in the directory, the Cv2 initiates a callout on the cellular network and then maintains the call until the last command in the line is executed.
Dial can only appear as the first entry in the list.
Default Dial value: 0000
Wait
The Wait command is used to insert delays into the sequence. Associated with the Wait command is the time delay in seconds; range of the delay is from 0 to 255 seconds.
Wait can be a single entry on a line but if it is entered in a line with other commands it must be preceded by a Dial command.
Default Wait value: 0000
B1272M001 | BARNETT ENGINEERING LTD. | ProTalk Cv2 |