Operations Overview |
1.9 Indicators
The Cv2 has four LED indicators to show the operation of the unit and assist in troubleshooting.
When the Cv2 is initially powered up, the four LEDs will do the following:
&All will turn on for approximately one second.
&Hook will flash on and off for one second then go out.
&Tone will flash on and off for one second then go out.
&Voice will flash on and off for one second then go out.
&Alarm will flash on and off for one second then go out.
& Hook
& Tone
& Voice
&Alarm If an unacknowledged alarm is present, the alarm indicator will flash. When the alarm is acknowledged, Alarm is on steady. When no alarms are present, Alarm is off.
1.10Troubleshooting
Is there power to the unit?
When power is first applied to the Cv2, it will flash the Hook indicator until it establishes contact with the cellular service. At any other time, the presence of power, and correct operation, are indicated by the brief flashing of the Voice LED every second.
Does the cell phone work?
Use the local call feature to determine if the unit is working properly. If the call cannot be completed, query the cell phone to see if it responds - any parameter can be used here. Query the RSSI (Received Signal Strength Indicator) in the phone to see if there is coverage in the area. The message “error” will be returned if there is no coverage. This can possibly be corrected by improving the antenna system.
B1272M001 | BARNETT ENGINEERING LTD. | ProTalk Cv2 |