Chapter 1: Specifications

1. Specifications

General Specifications

Approvals

FCC Part 15, Class A, CE, NEMA TS2, UL® Class 1, Division 2, Groups A, B, C, and D

 

 

Compatible

Windows® XP (32/64 bit), 2003 Server (32/64 bit), Windows Vista® (32/64 bit),

Operating Systems

2008 Server (32/64 bit), Windows 7 (32/64 bit)

 

 

Configuration

Via serial port using Modbus Hardened Serial Server Software, via network using Modbus Hardened Serial

Options

Server Software with an Ethernet connection or a standard Web browser such as Internet Explorer® 7, 8, or 9,

 

or Firefox® 3 or 4

 

 

Enclosure

Rating: IP30;

 

Mounting: DIN rail mount (35 mm)

 

 

User Controls

(1) Reset button

 

 

Connectors

(1) DB9 M, (1) 5-pin terminal block, (1) RJ-45, (1) 2-position pluggable terminal block for power

 

 

Indicators

(3) LEDs: (1) Ready, (1) Serial, (1) Ethernet Link

 

 

Temperature

Operating: -40 to +176° F (-40 to +80° C);

Tolerance

Storage: -40 to +185° F (-40 to +85° C);

 

Maximum Ambient Surrounding Air Temperature: 176° F (80° C)

 

 

Operating

10 to 95%, noncondensing

Humidity

 

 

 

Power

Voltage requirements: 10 to 48 VDC (58 VDC max.) extermal power supply;

 

Consumption: 4.0 watts maximum;

 

Terminal blocks: Wire size: 28 to 16 AWG,

 

Wire Type: Copper wire only,

 

Tightening Torque: 5 kg-cm,

 

Wire Temperature Rating: 105° C minimum, sized for 60° C ampacity

 

NOTE: One conductor per terminal.

 

 

Dimensions

1.2"H x 3.3"W x 4.7"D (4.6 x 12.2 x 17.1 cm)

 

 

Serial Interface Specifications

Baud Rates

75, 150, 300, 600, 1200, 2400, 4800, 7200, 9600, 14400, 19200, 28800, 38400, 57600, 115200, 230400

 

 

Data Bits

5, 6, 7, 8

 

 

Flow Control

None, RTS/CTS, X-ON/X-OFF

 

 

Mode Selection

RS-232/422/485 software-selectable

 

 

Parity

None, even, odd, mark, space

 

 

RS-232 Lines

TXD, RXD, RTS, CTS, DTR, DSR, DCD, GND

 

 

RS-422 Lines

TXDA(-), TXDB(+), RXDA(-), RXDB (+), GND

 

 

RS-485 (2-Wire)

Data(-), Data(+), GND

 

 

RS-485 (4-Wire)

TXDA(-), TXDB(+), RXDA(-), RXDB (+), GND

 

 

RS-422/485 Biasing

Auto 4.7 K-ohm pullups and pulldowns

 

 

RS-422/485

Auto termination with through hole (user supplied)

Termination

 

 

 

RS-485 Data

Auto control via MCU

Control

 

 

 

Stop Bits

1, 1.5, 2

 

 