APPENDIX F: Rackmounting the Matrix ServSwitch

Appendix F:

Rackmounting the

Matrix ServSwitch

You can use a ServSwitch Rackmount Kit to mount a Matrix ServSwitch in a 19", 23", or 24" rack. Use the RMK19B, RMK23B, or RMK24B Kit respectively to mount a 2 x 4 or 2 x 8 Switch; use the RMK19C, RMK23C, or RMK24C respectively to mount a 2 x 16 Switch. Each of these Kits consists of two rackmounting “ears” and four screws.

Keep these guidelines in mind when you mount the Switch:

The Switch is designed to work in ambient temperatures up to 50˚C (122˚F).

Leave at least one rack unit (1U, 1.75", 4.4 cm) of empty vertical space between Switch chassis and each other or other equipment.

Consider installing 1U-size rack-vent panels between Switches to provide them with adequate airflow.

Keep the front and rear doors closed on racks equipped with forced-air blowers or fans.

Tighten all connectors securely and provide adequate strain relief for all cables.

Provide a grounded power source for all Switches. Pay special attention to the load ratings of all equipment you plug into this power source: Overloaded circuits are potential fire hazards and can cause equipment failure and poor performance.

109