FIRE HAZARD

INSTALLATION (continued)

DANGER

FIRE HAZARD

THE FIRE SUPPRESSION SYSTEM MUST BE CHARGED AND CERTIFIED BY AN AUTHORIZED ANSUL® DISTRIBUTOR. NEVER ATTEMPT TO MODIFY OR BYPASS THE FIRE SUPPRESSION SYSTEM.

AN UNCONTROLLED FIRE CAN CAUSE SERIOUS INJURY, DEATH AND/OR PROPERTY LOSS.

IMPORTANT: The FIRE SUPPRESSION SYSTEM must be SET-UP and CHARGED by an authorized Ansul® distributor before the ventilator blower will operate.

NOTE: If the fire suppression system is discharged, a buzzer will sound continu- ously and the cooking appli- ance will remain inoperable until the fire suppression sys- tem is serviced. Recharging and resetting must be per- formed by an authorized Ansul® distributor ONLY.

Charging of the Ansul Fire Suppression system must be in accordance with Ansul® Design, Installation, Recharge and Maintenance Manual. (Ansul® #418087-05)

FIRE SUPPRESSION SYSTEM INSTALLATION

1.Any REMOTE MANUAL PULL STATION must be installed by an authorized ANSUL® distributor in accordance with the

AUTHORITY HAVING JURISDICTION.

NOTE: If a REMOTE MANUAL PULL STATION is installed, moving the unit for servicing will cause the Ansul® system to discharge. In this case, the unit must only be installed with four fixed legs

(i.e. remove rear casters and replace with legs). Additional legs may be ordered through an Authorized Wells Service Agency. See page 31.

2. The FIRE SUPPRESSION SYSTEM is comprised of a pressurized cartridge &

container of liquid fire suppressant, with

associated plumbing and controls. It utilizes factory

installed FUSIBLE LINKS for automatic actuation, and a factory installed

MANUAL PULL STATION for manual actuation. Two NOZZLES are used to disperse the liquid fire suppression media.

3. When the fire suppression system activates, the fire

suppression media is

discharged, both the cooking appliance and the

ventilator are de-energized, and a buzzer will sound

continuously. The fire suppression media

will form an emulsion

designed to both smother Fig. 6 Fire Suppression System and cool the fire.

Call your Authorized Ansul® Distributor immediately for service.

NOTE: See page 26 for the Material Safety Data Sheet for the fire suppression agent.

4.The MANUAL PULL STATION and any similar REMOTE MANUAL PULL STATION will activate the fire suppression system when the ring on the pull station is pulled horizontally.

10

Page 12
Image 12
Bloomfield WVOC-2HSG, WVOC-2HFG Fire Suppression System Installation, INSTALLATION continued, Danger, Fire Hazard