Bradford-White Corp BNTH, BNTV SECTION Venting and Combustion Air, Combustion Air From Room

Models: Modulating Boiler BNTV BNTH

1 64
Download 64 pages 52.15 Kb
Page 12
Image 12
SECTION 3.

Page 12

BRADFORD WHITE CORP.

 

 

 

 

SECTION 3.

Venting and Combustion Air

3.1 Combustion Air

Brute Elite boilers and water heaters must have provisions for combustion and ventilation air in accordance with the applicable requirements for Combustion Air Supply and Ventilation in the National Fuel Gas Code, ANSI Z223 1; or in Canada, the Natural Gas and Propane Installation Code, CSA B149.1. All applicable provisions of local building codes must also be adhered to.

A Brute Elite unit can take combustion air from the space in which it is installed, or the combustion air can be ducted directly to the unit. Ventilation air must be provided in either case.

3.1.1Combustion Air From Room

In the United States, the most common

requirements specify that the space shall communicate with the outdoors in accordance with method 1 or 2, which follow. Where ducts are used, they shall be of the same cross-sectional area as the free area of the openings to which they connect.

HORIZONTAL INTAKE AND EXHAUST PVC VENT TERMINAL KITS

SIZE

2" PVC

3" PVC

4" PVC

6" PVC

Standard

Concentric

Standard

Concentric

Standard

Standard

 

 

CA006000

CA005900 239-44069-01

 

 

80

included

optional

optional

optional

n/a

n/a

 

 

 

 

 

 

 

105

included

optional

optional

optional

n/a

n/a

150

n/a

n/a

included

optional

n/a

n/a

 

 

 

 

 

 

 

199/210

n/a

n/a

included

optional

n/a

n/a

 

 

 

 

 

 

 

285

n/a

n/a

optional

optional

included

n/a

399

n/a

n/a

n/a

n/a

included

n/a

 

 

 

 

 

 

 

500

n/a

n/a

n/a

n/a

included

n/a

 

 

 

 

 

 

 

600

n/a

n/a

n/a

n/a

included

optional

750

n/a

n/a

n/a

n/a

n/a

included

 

 

 

 

 

 

 

850

n/a

n/a

n/a

n/a

n/a

included

 

 

 

 

 

 

 

Concentric vent terminal = 10 ft. pipe length.

Method 1: Two permanent openings, one

commencing within 12" (300mm) of the top and one commencing within 12" (300mm) of the bottom, of the enclosure shall be provided. The openings shall communicate directly, or by ducts, with the outdoors or spaces that freely communicate with the outdoors. When directly communicating with the outdoors, or when communicating to the outdoors through vertical ducts, each opening shall have a minimum free area of 1 square inch per 4000 Btu/hr (550 square mm/kW) of total input rating of all equipment in the enclosure. When communicating to the outdoors through horizontal ducts, each opening shall have a minimum free area of not less than 1 square inch per 2000 Btu/hr (1100 square mm/kW) of total input rating of all equipment in the enclosure.

Method 2: One permanent opening, commencing within 12" (300mm) of the top of the enclosure, shall be permitted. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that directly communicate with the outdoors and shall have a minimum free area of 1 square inch per 3000 Btu/hr (734 square mm/kW) of the total input rating of all equipment located in the enclosure. This opening must not be less than the sum of the areas of all vent connectors in the confined space.

Other methods of introducing combustion and ventilation air are acceptable, providing they conform to the requirements in the applicable codes listed above.

In Canada, consult local building and safety codes or, in absence of such requirements, follow CAN/CGA B149.

3.1.2 Ducted Combustion Air

The combustion air can be taken through the wall, or through the roof. When taken from the wall, it must be taken from out-of-doors by means of the horizontal wall terminal, shown in Table(s) 3. See Table 2 to select the appropriate diameter air pipe. When taken from the roof, a field-supplied rain cap or an elbow arrangement must be used to prevent entry of rain water (see Figure10).

Use ABS, PVC, CPVC or galvanized pipe for the

Table 3a. PVC Vent Terminal Kits.

SIZE

PRO TECH (FasNSeal)

 

HEAT FAB (Saf-T-Vent)

 

 

Z FLEX (Z-Vent)

 

 

Boiler

 

Flue

Intake Air

Boiler

Intermediate

Flue

Intake Air

Boiler

Flue

Intake Air

 

 

Adapter

Termination

Termination

Adapter

Adapter

Termination

Termination

Adapter

Termination

Termination

399-600

F303759

 

FSBS4

FSAIH04

KB285600

9454BUREZ-1*

9492

9414TERM

2SVSLA04

2SVSTP04

2SVSTEX0490

 

 

FSRC4(R.C)

303888

 

 

5400CI

 

 

2SVSRCX04

 

 

750-850

F303759

 

FSBS6

FSAIH04

Table 3b. Approved Stainless Steel Terminations and Adapters.

(intake only)

 

303888

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INSTALLATION STANDARDS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MATERIAL

 

 

UNITED STATES

 

 

 

CANADA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ABS

 

 

ANSI/ASTM D1527

 

 

 

 

 

 

 

PVC, sch 40

 

ANSI/ASTM D1785 or D2665

 

Air pipe material must be chosen

 

 

CPVC, sch 40

 

 

ANSI/ASTM F441

 

based upon the intended application of the boiler.

Single wall galv. steel

 

 

26 gauge

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 4. Required Combustion Air Pipe Material.

Page 12
Image 12
Bradford-White Corp BNTH, BNTV warranty SECTION Venting and Combustion Air, Combustion Air From Room, Ducted Combustion Air