Bradford-White Corp BNTH, BNTV warranty Boiler Pump Interrupt, Lead Lag Setpoint, Lead Lag Address

Models: Modulating Boiler BNTV BNTH

1 64
Download 64 pages 52.15 Kb
Page 39
Image 39
8.12.1 Lead Lag Setpoint

Brute Elite

Page 39

 

 

8.12.2Lead Lag Master/Slave Selection DANGER

Water temperature over 125°F (52°C) can cause severe burns instantly or death from scalds.

Children, disabled and elderly are at hightest risk of being scalded.

See instruction manual before setting temperature at heating appliance.

Feel water before bathing or showering.

If this appliance is used to produce water that could scald if too hot, such

as domestic hot water use, adjust the outlet

control (limit) or use temperature limiting valves to obtain a maximum water temperature of 125°F (52°C).

operation there are several settings in the "setup" menu structure that must be adjusted for the specific installation, each is covered in the following sections.

8.12.1 Lead Lag Setpoint

The lead lag setpoint is set from the "user" menu using the "LL" variable. This is the temperature the boiler is attempting to maintain at the system sensor. This setting doesn't control the boiler outlet temperature, so the water temperature at the boiler outlet may be much hotter than the system temperature setpoint. Adjust the LL setpoint to the desired operating temperature of the system.

8.12.2Lead Lag Master/Slave Selection

In the SETUP menu structure, the "LL" menu

allows the lead lag system to be turned on and the boiler to be configured as a master or slave control. In each lead lag system there can only be one master control, so proper selection is important to avoid operating issues. To set the boiler to lead lag "master" operation the LL menu should be set to "LDR". To set the boiler to slave, "SLA" should be selected.

8.12.3 Lead Lag Address

The Lead Lag address must be set for each boiler connected to the lead lag system. Each boiler must have a unique address selected for the system to work properly. Typically, the lead or master boiler should be set to address one and the remaining boilers should be set to values 2–8 depending upon how many boilers are installed in the system.

8.12.4 Lead Lag Hysteresis

The lead lag system uses a hysteresis value set in the setup menu, called, "HS". The hysteresis and setpoint values control the on and off points of the boiler. If the lead lag setpoint is adjusted to 120°F with a hysteresis value of 5°F the boiler will turn off when the water temperature reaches 125°F and will turn back on when the water temperature reaches 115°F. Set the hysteresis values to match the boiler to the system operating characteristics. Setting this value correctly

will help reduce the chance of short cycling.

8.12.5 Lead Lag Base Load Setting

The lead lag system uses a base load setting that is set through the "setup" menu called "bL". The base load setting identifies the firing rate that the operating boiler must achieve before the next boiler in the system is allowed to operate. The default setting is 50% to avoid short cycling and operating the boilers at higher, less efficient, firing rates.

8.13 Boiler Pump Interrupt

8.12.3 Lead Lag Address WARNING

Failure to plumb, pump and install the appliance correctly when using this feature may lead to reduced or no water flow through the heat exchanger, causing premature failure of the heat exchanger, personal injury or death. Please consult the factory with any questions regarding the use of this feature.

The boiler pump interrupt feature is used in some applications when the boiler is being used for both hydronic and domestic hot water heating. The interrupt jumper is used to turn off the boiler pump during a domestic hot water demand. For this to work properly the system must be plumbed and pumped to allow the domestic hot water pump to supply the flow and head requirements for the boiler and indirect water heater together. It is not necessary to use the interrupt jumper in all applications. Specific modes of operation that may require the use of this feature are shown in Section 6.

NAME

FUNCTION

VALUE

CH on

Burner demand begins when the

5°F

differential

outlet water temperature reaches

 

 

"Outlet water temperature setpoint"

 

 

minus "CH on differential"

 

CH off

Burner demand ends when the

5°F

differential

outlet water temperature reaches

 

 

"Outlet water temperature setpoint"

 

 

plus "CH off differential"

 

DHW on

Burner demand begins when the

2°F

differential

outlet water temperature reaches

(80-285)

 

"Outlet water temperature setpoint"

5°F

 

minus "DHW on differential"

(399-850)

DHW off

Burner demand ends when the

10°F

differential

outlet water temperature reaches

(80-285)

 

"Outlet water temperature setpoint"

5°F

 

plus "DHW off differential"

(399-850)

Pump

Operates the pump for the overrun

1 or 5

overrun

time after the burner demand

minutes

 

has ended

 

High

Locks the boiler out when the high

200°F

limit

limit temperature is reached

 

 

(requires manual reset)

 

Flame

Flame signals lower than the flame

0.8Vdc

threshold

threshold interrupt burner operation

 

DHW

Time for domestic hot water priority

60 min.

priority time

 

 

 

Table 15. Default Control Settings.

 

Page 39
Image 39
Bradford-White Corp BNTH, BNTV Boiler Pump Interrupt, Lead Lag Setpoint, Lead Lag Master/Slave Selection, Lead Lag Address