Brute Elite | Page 15 |
|
|
1.Figure 12 shows the requirements for mechanical vent terminal clearances for the U.S. and Canada.
2.Vent terminals for condensing appliances or appliances with condensing vents are not permitted to terminate above a public walkway, or over an area where condensate or vapor could create a nuisance or hazard.
3.Locate the vent terminal so that vent gases cannot be drawn into air conditioning system inlets.
4.Locate the vent terminal so that vent gases cannot enter the building through doors, windows, gravity inlets or other openings. Whenever possible, avoid locations under windows or near doors.
5.Locate the vent terminal so that it cannot be blocked by snow. The installer may determine that a vent terminal must be higher than the minimum shown in codes, depending upon local conditions.
6.Locate the terminal so the vent exhaust does not settle on building surfaces or other nearby objects. Vent products may damage surfaces or objects.
7.If the boiler or water heater uses ducted combustion air from an intake terminal located on the same wall, see Figures
If the vent termination is located in an area exposed to high winds, an optional PVC tee (the same diameter as the vent pipe) may be used. The tee'd vent termination offers greater protection from wind related operating issues.
3.3.2Side Wall Combustion Air Terminal
The side wall combustion air terminal, or
concentric terminal (see Table 3), must be used when the heater takes air from a side wall. Contact Bradford White for
14):
1.Do not locate the air inlet terminal near a source of corrosive chemical fumes (e.g., cleaning fluid, chlorine compounds, etc.)
2.Locate the terminal so that it will not be subject to damage by accident or vandalism. It must be at least 7 feet (2.1m) above a public walkway.
3.Locate the combustion air terminal so that it cannot be blocked by snow. The National Fuel Gas Code requires that it be at least 12 inches (30cm) above grade, but the installer may determine it should be higher, depending upon local conditions.
4.If the Brute Elite is
5.For concentric vent, follow instructions included with vent kit.
6.Multiple vent kits should be installed such that the horizontal distance between outlet group and inlet group is 36" (90cm) (see Figure 13).
7.Vent outlet for models
12" (30cm) away from the air inlet. Vent outlets for models
3.3.3 Vertical Vent Terminal
When the unit is vented through the roof, the vent must extend at least 3 feet (0.9m) above the point at which it penetrates the roof. It must extend at least 2 feet (0.6m) higher than any portion of a building within a horizontal distance of 10 feet (3.0m), and high enough above the roof line to prevent blockage from snow. The vent terminal included with the Brute Elite can be used in both vertical and horizontal applications. When the combustion air is taken from the roof, the combustion air must terminate at least 12" (30cm) below the vent terminal (see Figure 11).
3.3.4Vertical Combustion Air Terminal
When combustion air is taken from the roof, a
(30cm) above the point at which it penetrates the roof, and high enough above the roof line to prevent blockage from snow. When the vent terminates on the roof, the combustion air must terminate at least 12" (30cm) below the vent terminal.
3.3.5 Installations in the Commonwealth of Massachusetts
In Massachusetts the following items are required if the
1.Installation of Carbon Monoxide Detectors At the time of installation of the side wall vented gas fueled appliance, the installing plumber or gas- fitter shall observe that a
a.In the event that the
b.In the event that the requirements of the subdivi- sion cannot be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements,