Brute Elite | Page 43 |
|
|
SECTION 10.
Operating Instructions
10.1 Filling the Boiler System
1.Ensure the system is fully connected. Close all bleeding devices and open
2.If
3.If a water pressure regulator is provided on the
4.Open bleeding devices on all radiation units at the high points in the piping throughout the system, unless automatic air bleeders are provided at such points.
Note that there is an air bleed located on the left side of Brute Elite, on top of the water manifold.
5.Cycle the boiler pump on and off 10 times, 10 seconds on and 10 seconds off to remove all air from the heat exchanger. Then run system and appliance pump for a minimum of 30 minutes with the gas shut off.
WARNING
Failure to remove all air from the heat exchanger could lead to property damage, severe injury or death.
6.Open all strainers in the circulating system, check flow switch operation (if equipped), and check for debris. If debris is present, clean out to ensure proper circulation.
7.Recheck all air bleeders as described in Step 4.
8.Check liquid level in expansion tank. With the system full of water and under normal operating pressure, the level of water in the expansion tank should not exceed ¼ of the total, with the balance filled with air.
9.Start up boiler according to the procedure in this manual. Operate the entire system, including the pump, boiler, and radiation units for one (1) hour.
10.Recheck the water level in the expansion tank. If the water level exceeds ¼ of the volume of the expansion tank, open the tank drain, and drain to that level.
11.Shut down the entire system and vent all radiation units and high points in the system piping, as described in Step 4.
12.Close
13.Check gauge for correct water pressure and also check water level in the system. If the height indicated above the boiler insures that water is at the highest point in the circulating loop, then the system is ready for operation.
14.Prime condensate trap with water (not required for BNTH 600, 750, 850).
15.Refer to local codes and the
16.After placing the unit in operation, the ignition system safety shutoff device must be tested.
First, shut off the manual gas valve, and call the unit for heat. Main gas terminals will be energized, attempting to light, for four (4) seconds, and then will
Second, turn the power off, press the manual reset button on the boiler control, or the user display, open the manual gas valve and allow the unit to light. While the unit is operating, close the manual gas valve and ensure that power to the main gas valve has been cut.
17.Within three (3) days of
Important Note: The installer is responsible for identifying to the owner/operator the location of all emergency shutoff devices.
WARNING
Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance
and to replace any part of the control system and any gas control that may have been
under water.
10.2 Operating the Burner and Set Up
Initial setup must be checked before the unit is put in operation. Problems such as failure to start, rough ignition, strong exhaust odors, etc. can be due to improper setup. Damage to the boiler resulting from improper setup is not covered by the limited warranty.
10.2.1 Burner Operation
REQUIRED TOOLS: differential pressure gauge capable of reading negative 0.01 inches W.C. (0.002kPa), screw drivers, torx bits, combustion analyzer.
1.Using this manual, make sure the installation is complete and in full compliance with the instructions and all local codes.
2.Determine that the appliance and system are filled with water and all air has been bled from both. Open all valves.
3.Observe all warnings on the Operating Instructions