Brute Elite | Page 37 |
|
|
SECTION 8.
Brute Elite Control Setup
and Operation
The Brute Elite control is an integrated electronic control that replaces many of the individual components found on older appliances. The control acts as the ignition control, pump control, high limit and cascading/ lead lag control and is setup using the display on the appliance.
Once the value is adjusted the NEXT or DONE button can be pressed. The DONE button returns you to the Home screen. The NEXT button increments the display to the next item in the menu structure.
USER mode is the home screen shown on the control. If the display is not in USER mode wait for the display timeout period to be reached or press the Done button to return to the USER menu.
SETUP mode is accessed by holding the up and down arrow keys simultaneously for 3 seconds.
DIAGNOSTIC mode is accessed by holding the NEXT button for 3 seconds.
Figure 31. Control Buttons on User Interface.
8.1 Display Navigation
The display is divided into three menu structures, USER, SETUP and DIAGNOSTIC. The menu structure and variables in each are shown in Tables
MENU ITEM | FUNCTION | RANGE | DEFAULT |
Outlet water | Displays the current outlet | 120°F | |
temperature | water temperature & allows |
|
|
| the setpoint to be adjusted |
|
|
Inlet water | Displays the current inlet | — | — |
temperature | water temperature |
|
|
Delta T | Displays the current | — | — |
| temperature rise across |
|
|
| the heat exchanger |
|
|
DHW water | Displays the current DHW | 120°F | |
temperature | temperature & allows the |
|
|
| setpoint to be adjusted |
|
|
Stack | Displays the current stack | — | — |
temperature | temperature |
|
|
Outdoor | Displays the current outdoor | — | — |
temperature | air temperature |
|
|
LL | Displays the current system | 120°F | |
| temperature and allows the |
|
|
| setpoint to be adjusted |
|
|
Firing Rate | Displays an indicator of the | — | — |
| current firing rate based |
|
|
upon fan RPM. The actual firing rate may vary.
Table 12. User Mode Menu Structure.
8.2 Ignition Control- Sequence of Events
1.Call for heat
2.Safety chain check
3.Fan starts and waits to achieve prepurge RPM
MENU ITEM | DEFINITION |
F or C | Selects temperature units |
LBTHODLOD | Outdoor reset enable/disable - |
| enables menu items |
LBT | Low boiler setpoint during outdoor reset |
| see Figure 29 |
HOD | High outdoor temperature setpoint |
| see Figure 29 |
LOD | Low outdoor temperature setpoint |
| see Figure 29 |
RMT Add | Used for Lead/Lag (follow menus) |
LL | Lead/Lag enable/disable - enables menu items |
HS | Hysteresis - temp range between on/off cycles |
bL | Base Load % - input rate before next boiler fires |
Sd | Warm weather |
ASC | Anti short cycle - minutes of delay between |
| startup |
bAC | Future use - Press DONE to exit menu. |
PAS | Future use - Press DONE to exit menu. |
NOTE: When enabling/disabling functions, select "Done" and wait 30
seconds before scrolling.
Table 13. Setup Mode Parameters.
MENU ITEM | DESCRIPTION |
mA | Display the flame sense signal |
Alert codes | Displays the current alert code |
Lockout code | Displays the current lockout code |
Outlet Limit | Displays outlet temperature limit |
DHW limit | Displays Domestic Hot Water limit setting |
Stack Limit | Displays Stack limit setting |
Min. firing rate | Displays the minimum firing rate allowed |
Min. forced | Allows the user to force the boiler to fire at |
firing rate | the minimum firing rate |
Max forced | Allows the user to force the boiler to fire at |
firing rate | the maximum firing rate |
Rate indicator | Displays a indicator of the firing rate based |
| off of the fan RPM. Actual firing rate may |
| vary depending upon setup. |
Table 14. Diagnostic Mode Menu Structure.