Bradford-White Corp Modulating Boiler, BNTH continued next page, Code#, Problem, Probable Cause

Models: Modulating Boiler BNTV BNTH

1 64
Download 64 pages 52.15 Kb
Page 50
Image 50
CODE#

Page 50

 

BRADFORD WHITE CORP.

 

 

 

 

 

 

 

 

 

 

 

 

CODE#

PROBLEM

PROBABLE CAUSE

SOLUTION

 

 

 

 

 

COMMON LOCKOUT CODES

27

Internal error

Flame rod to ground

Check wiring / probe grounded, dirty probe

47

Flame rod to ground leakage

Faulty flame detector

Clean or replace flame detector

49

24VAC voltage low/high

Faulty transformer

Check/correct supply line voltage; replace faulty

 

 

 

transformer

52

Motor tachometer fault

Faulty fan / fan wiring

Check fan harness wiring for continuity; replace faulty

 

 

fan circuit

 

53

AC inputs phase reversed

 

Reverse 24V hot/neutral - use common ground

61

Anti short cycle

Call for heat will be held

Change ASC timer setting

 

 

until timer resets

 

62

Fan speed not proved

Dirty / defective fan

Clean or replace fan; check wiring

63

LCI off

Safety chain interrupt

Check flow switch, aux high limit, LWCO, gas

 

 

 

pressure switches, condensate level and correct

 

 

 

problem

69

Outlet high limit

High limit tripped

Determine cause: low/no flow, valves closed, settings

 

 

 

and correct

79

Outlet high limit

 

Check pump, time delay, valves closed, etc. and

80

DHW high limit

High limit reached

correct overtemp

81

Delta T inlet/outlet limit

 

 

 

82

Stack limit

High limit reached

Could be caused by high ambient temperature, or

 

 

 

high return water temperature

88

Outlet T-rise limit

High limit reached

Diagnose / repair cause of high temperature

90

Heat exchanger high limit

 

 

91

Inlet sensor fault

 

 

92

Outlet sensor fault

Faulty sensor or wiring

Check wiring / replace sensor; condition can be

93

DHW sensor fault

 

caused by short

95

Stack sensor fault

 

 

 

96

OAT temperature sensor fault

Faulty outdoor air

Check wiring and sensor for short; replace sensor

 

temperature sensor

is open or shorted

 

105

Flame detected

Flame exists at burner

Clean burner of soot or other debris that could

 

out of sequence

when it should not be

maintain flame

106

Flame lost in MFEP

Unstable flame during

 

 

 

 

107

Flame lost early in Run

lighting / flame proving

Check venting, gas supply pressure, burner, fan, etc.

 

 

sequence

 

108

Flame lost in Run

 

 

 

109

Ignition failed

Problem with ignitor, or

Check / replace ignitor, wiring; check for shorting

 

 

other ignition-related device

in ignitor cable

113

Flame circuit timeout

Flame not established

Check all combustion components; purge gas;

 

 

within expected time limit

check ignition source

122Lightoff rate proving failed

123Purge rate proving failed

128

Fan speed failed / prepurge

Fan did not reach

Check fan wiring; replace fan

129

Fan speed failed / preignition

expected RPM

 

 

 

130

Fan speed failed / ignition

 

 

131

Fan movement detected

Fan should not be moving

Check for common venting problems or otherwise

 

during standby

when not powered

forced air

132

Fan speed failed during run

Fan lost or gained speed

Fan overheating or otherwise failing; check cable;

 

 

during run sequence away

replace fan

 

 

from control spec

 

137

ILK failed to close

No power at interlock ILK

Check J5 pin 1 for power - if no power, confirm

 

 

 

safeties are closed

continued next page >

Page 50
Image 50
Bradford-White Corp Modulating Boiler continued next page, Code#, Problem, Probable Cause, Solution, Common Lockout Codes