Honeywell Gas Control Troubleshooting Chart

LED Status Control Status Probable Cause

Five flashes and
three second
pause
Thermostat/well sensor fault.
Gas Control electronic fault
detected.
Seven flashes and
three second
pause
Eight flashes and
three second
pause
Standing pilot remains on while set
point knob is in “OFF” position.
1. Damage to the temperature
sensor.
2. Temperature sensor resistance
out of range.
1. Control need to be reset.
2. Control is wet or physically
damaged.
Pilot valve stuck in open position.

Service

Procedure

1. Seeservice
procedure RG-VI
1. Reset Gas Control
2. Replace Gas
Control.
Replace Gas Control.
Flammable Vapor Ignition Resistant Water Heaters
Green LED Indicator

Observe green LED indicator on

Gas Control. Error flash codes are

displayed with a three secondpause

before repeating. Check and repair

the system as noted in the

troubleshooting table below.

6
Water leak detectedby accessory
module.
Six flashes and
three second
pause
Excessive amount of water in drain
pan/water dam.
1. Check T&P valve
2. Check all water
fittings.
3.Pressurize and leak
test tank.
6
6