569J

ELECTRICAL DATA (cont.)

569J*16A COOLING WITHOUT POWERED CONVENIENCE OUTLET

V---Ph---

Hz

VOLTAGE RANGE

COMP 1

COMP 2

 

OFM (ea)

POWER SUPPLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MIN

MAX

RLA

LRA

RLA

LRA

 

WATTS

FLA

MCA

Fuse

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230---

3---

60

187

253

25

164

25

164

 

325

1.5

60.8

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460---

3---

60

414

506

12.2

100

12.2

100

 

325

0.8

29.9

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575---

3---

60

518

633

9

78

9

78

 

325

0.7

22.4

30

 

 

 

 

 

 

 

 

 

 

 

 

569J*16A COOLING WITH POWERED CONVENIENCE OUTLET

 

 

 

 

V---Ph---

Hz

VOLTAGE RANGE

COMP 1

COMP 2

OFM (ea)

POWER SUPPLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MIN

MAX

RLA

LRA

RLA

LRA

WATTS

FLA

MCA

Fuse

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230---

3---

60

187

253

25

164

25

164

325

1.5

66.6

90

 

 

 

 

 

 

 

 

 

 

 

 

 

460---

3---

60

414

506

12.2

100

12.2

100

325

0.8

32.1

40

 

 

 

 

 

 

 

 

 

 

 

 

 

575---

3---

60

518

633

9

78

9

78

325

0.7

24.1

30

 

 

 

 

 

 

 

 

 

 

 

569J*16D COOLING WITHOUT POWERED CONVENIENCE OUTLET

 

 

 

V---Ph---

Hz

VOLTAGE RANGE

COMP 1

COMP 2

 

OFM (ea)

POWER SUPPLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MIN

MAX

RLA

LRA

RLA

LRA

 

WATTS

FLA

MCA

Fuse

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230---

3---

60

187

253

25

164

25

164

 

325

1.5

60.7

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460---

3---

60

414

506

12.2

100

12.2

100

 

325

0.8

29.8

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575---

3---

60

518

633

9

78

9

78

 

325

0.6

22.0

30

 

 

 

 

 

 

 

 

 

 

 

 

569J*16D COOLING WITH POWERED CONVENIENCE OUTLET

 

 

 

 

V---Ph---

Hz

VOLTAGE RANGE

COMP 1

COMP 2

OFM (ea)

POWER SUPPLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MIN

MAX

RLA

LRA

RLA

LRA

WATTS

FLA

MCA

Fuse

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230---

3---

60

187

253

25

164

25

164

325

1.5

65.6

90

 

 

 

 

 

 

 

 

 

 

 

 

 

460---

3---

60

414

506

12.2

100

12.2

100

325

0.8

32.1

40

 

 

 

 

 

 

 

 

 

 

 

 

 

575---

3---

60

518

633

9

78

9

78

325

0.7

24.1

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

46