AHRI* CAPACITY RATINGS

 

COOLING

 

NOM.

NET COOLING

TOTAL

 

 

UNIT

COMPRESSORS

CAPACITY

CAPACITY

POWER

EER

IEER

CIRCUITS

 

 

 

(TONS)

(MBH)

(kW)

 

 

569J*07A/524J*07

1

1

6

71.0

6.2

11.5

12.2

 

 

 

 

 

 

 

 

569J*08A/524J*08

1

1

7.5

92.0

8.2

11.2

11.8

 

 

 

 

 

 

 

 

569J*12A/524J*12

1

1

10

117.0

10.4

11.2

12.0

 

 

 

 

 

 

 

 

569J*14A/524J*14

1

1

12.5

148.0

13.5

11.0

12.0

 

 

 

 

 

 

 

 

569J*16A/524J*16

1*

2

15

184.0

16.4

11.2

13.2

 

 

 

 

 

 

 

 

569J*25A/524J25

1*

2

20

240.0

21.8

11.0

11.2

 

 

 

 

 

 

 

 

* Single circuit with two (tandem) compressors. See application tip #38TIP---10---03 for staging capabilities.

 

 

 

 

 

 

 

 

 

 

COOLING

 

NOM.

NET COOLING

TOTAL

 

 

UNIT

COMPRESSORS

CAPACITY

CAPACITY

POWER

EER

IEER

CIRCUITS

 

 

 

(TONS)

(MBH)

(kW)

 

 

569J*12D/524J12

2

2

10

117.0

10.4

11.2

11.6

 

 

 

 

 

 

 

 

569J*14D/524J14

2

2

12.5

148.0

13.5

11.0

12.0

 

 

 

 

 

 

 

 

569J*16D/524J16

2

2

15

184.0

16.4

11.2

11.8

 

 

 

 

 

 

 

 

569J*25D/524J25

2

2

20

240.0

21.8

11.0

11.2

 

 

 

 

 

 

 

 

LEGEND

 

 

NOTES

 

 

 

569J

AHRI

--- Air Conditioning, Heating and Refrigeration

 

Institute

ASHRAE

--- American Society of Heating, Refrigerating

 

and Air Conditioning, Inc.

EER

--- Energy Efficiency Ratio

IEER

--- Integrated Energy Efficiency Ratio

1.Rated in accordance with AHRI Standard 340/360, as appropriate.

2.Ratings are based on:

Cooling Standard: 80_F (27_C) db, 67_F (19_C) wb indoor air temp and 95_F (35_C) db outdoor air temp. IEER Standard: 80_F (27_C) db, 67_F (19_C) wb indoor air temp and 4 various outdoor temperatures.

3.All units comply with ASHRAE 90.1 Energy Standard for minimum EER and IEER requirements.

SOUND POWER LEVELS, dB

UNIT

COOLING CIRCUITS

OUTDOOR SOUND (dB)

A---WEIGHTED 63 125 250 500 1000 2000 4000 8000 NOVATION --- All Aluminum Coil Design

569J*07A

1

82

86.4

86.0

79.2

80.2

77.6

72.0

67.9

62.3

569J*08A

1

82

86.8

85.7

80.3

80.3

77.7

72.3

70.2

65.4

569J*12A

1

82

82.8

81.5

79.2

79.4

76.2

72.3

69.4

64.2

569J*14A

1

82

82.9

78.5

77.0

77.0

75.6

75.9

72.3

70.9

569J*16A

1

80

90.3

81.8

78.0

76.7

75.2

70.5

66.4

61.9

569J*25A

1

85

91.0

85.0

80.0

86.0

79.0

73.0

68.0

63.0

569J*12D

2

82

85.2

84.0

81.0

79.5

76.6

72.4

69.3

69.5

569J*14D

2

82

84.7

79.8

78.8

77.6

77.0

72.5

70.3

67.3

569J*16D

2

80

90.3

81.8

78.0

76.7

75.2

70.5

66.4

61.9

569J*25D

2

85

91.0

85.0

80.0

86.0

79.0

73.0

68.0

63.0

 

 

RTPF --- Round Tube/Plate Fin Coil Design

 

 

 

 

 

569J*07A

1

85

89.3

85.0

82.0

82.7

80.2

75.2

71.0

66.0

569J*08A

1

85

89.3

85.0

82.0

82.7

80.2

75.2

71.0

66.0

569J*12A

1

83

86.6

81.9

85.7

80.0

77.1

74.6

69.2

65.8

569J*12D

2

84

86.3

85.8

81.4

81.9

79.5

75.1

71.9

68.9

569J*14D

2

83

81.7

80.9

82.2

80.4

78.2

73.6

69.7

65.4

569J*16A

2

83

86.7

81.2

78.9

80.4

78.0

74.2

70.2

65.0

569J*16D

2

83

86.7

81.2

78.9

80.4

78.0

74.2

70.2

65.0

569J*25A

2

85

91.0

85.0

80.0

86.0

79.0

73.0

68.0

63.0

569J*25D

2

85

91.0

85.0

80.0

86.0

79.0

73.0

68.0

63.0

LEGEND

 

 

 

 

 

 

 

 

 

 

dB = Decibel

 

 

 

 

 

 

 

 

 

 

NOTE: Outdoor sound data is measure in accordance with AHRI standard 270---2008.

5

Page 5
Image 5
Bryant 569J manual AHRI* Capacity Ratings, Sound Power LEVELS, dB, Cooling NOM NET Cooling, Unit Cooling Circuits