11

OPTIONS AND ACCESSORIES

569J* OPTIONS AND ACCESSORIES

ITEM OPTION* ACCESSORY†
Disconnect Switch (non-fused)}X
Special---coated Coil Protection X
Convenience Outlet (115-v)** X
Low Ambient Temperature
MotorMaster IrControl X X
Wired Condenser Coil Grille (Novation 07 --- 14 models only) X
Louvered Hail Guard X X
Programmable Thermostats X
* Factory-installed option.
Field-installed accessory.
}Non ---fused disconnect switch cannot be used when unit MOCP electrical rating exceeds 80 amps.
** Powered and non---powered versions available

569J* factory-installed options

CONDENSER COIL OPTIONS

Coil Coating Application -- Novation Coils

Coil Description
Environment
Standard
N o n --- C o r r o s i v e Mild Coastal Moderate
Coastal
Severe
Coastal Industrial Industrial &
Coastal
Alum Fin / Alum Tube X
E --- C o a t e d A l / A l X X X X X
NOTE: E---Coat is only available and must be used in any non---standard environment listed above.

Coil Coating Application -- Round Tube/Plate Fin Coils

(07,08, 12, 16, 25 models)

E n v i r o --- S h i e l d Description
Environment
Standard
N o n --- C o r r o s i v e Mild Coastal Moderate
Coastal
Severe
Coastal Industrial Industrial &
Coastal
Alum Fin / Cu Tube X
P r e --- C o a t e d A l / C u X
E --- C o a t e d A l / C u X X
Cu / Cu X X
NOTE: Refer to the Guide Specifications for further detail.
E-coated aluminum-fin coils have a flexible and durable
epoxy coating uniformly applied to all coil surfaces.
Unlike brittle phenolic dip and bake coatings, E-coating
provides superior protection with unmatched flexibility,
edge coverage, metal adhesion, thermal performance, and
most importantly, corrosion resistance.
E-coated coils provide this protection since all coil
surfaces are completely encapsulated from environmental
contamination. This coating is especially suitable in
industrial environments.
Pre--coated coils (RTPF coils only) provide protection in
mild coastal environments.
–20_F (–29_C) low-ambient temperature kit option
(MotorMaster Ir)controls outdoor-fan motor operation
to maintain the correct head pressure at low outdoor
ambient temperatures.
Louvered hail guard package protects coils against
damage from flying debris and hail.
115-v convenience outlet is used to power electric drills,
lights, and refrigerant recovery machines. This means that
a separate 115-v power supply is no longer necessary.
Non-fused disconnect switch is used to remove power
locally at the condensing unit. This switch also includes a
power lockout capability to protect the service person.
This lockout switch saves the service person time and
effort because there is no need to access a distant
disconnect switch while servicing the unit.
569J