569J
PHYSICAL DATA
Single Circuit Models with NOVATION |
| ||||
| 569J*07A | 569J*08A | 569J*12A | 569J*14A | 569J*16A |
Refrigeration System |
|
|
|
|
|
|
|
|
|
| |
# Circuits / # Comp. / Type | 1 / 1 / Scroll | 1 / 1 / Scroll | 1 / 1 / Scroll | 1 / 1 / Scroll | 1 / 2 /Scroll |
R | 4.4 | 4.9 | 6.3 | 7.3 | 12.2 |
System charge w/ fan coil | 8.4 | 10.2 | 13.8 | 18.0 | 24.6 |
Metering device | TXV | TXV | TXV | TXV | TXV |
630 / 505 | 630 / 505 | 630 / 505 | 630 / 505 | 630 / 505 | |
54 / 117 | 54 / 117 | 54 / 117 | 54 / 117 | 54 / 117 | |
|
|
|
|
|
|
Cond. Coil |
|
|
|
|
|
Material (Fin/Tube) | Al/Al | Al/Al | Al/Al | Al/Al | Al/Al |
Coil type | Novation | Novation | Novation | Novation | Novation |
Rows / FPI | 1 / 20.3 | 1 / 20.3 | 1 / 20.3 | 1 / 20.3 | 1 / 20.3 |
Total face area (ft2) | 17.5 | 20.5 | 25.0 | 31.8 | 25.0 x 2 |
|
|
|
|
|
|
Cond. fan / motor |
|
|
|
|
|
Qty / Motor drive type | 2 / direct | 2 / direct | 2 / direct | 2 / direct | 3 / direct |
Motor HP / RPM | 1/4 / 1100 | 1/4 / 1100 | 1/4 / 1100 | 1/4 / 1100 | 1/4 / 1100 |
Fan diameter (in) | 22 | 22 | 22 | 22 | 22 |
Nominal Airflow (cfm) | 6,000 | 6,000 | 6,000 | 6,000 | 10,000 |
Watts (total) | 610 | 610 | 610 | 610 | 970 |
Note: 569J*25 model is not available with NOVATION coil.
Single Circuit Models with RTPF |
| |||||
| 569J*07A | 569J*08A | 569J*12A | 569J*14A | 569J*16A | 569J*25A |
Refrigeration System |
|
|
|
|
|
|
|
|
|
|
|
| |
# Circuits / # Comp. / Type | 1 / 1 / Scroll | 1 / 1 / Scroll | 1 / 1 / Scroll | 1 / 1 / Scroll | 1 / 2 / Scroll | 1 / 2 / Scroll |
R | 11.0 | 13.0 | 16.0 | 32.0 | 32.0 | 28.0 |
System charge w/ fan coil* | 14.0 | 17.0 | 20.0 | N/A | 43.0 | 38.0 |
Metering device | TXV | TXV | TXV | TXV | TXV | TXV |
630 / 505 | 630 / 505 | 630 / 505 | 630 / 505 | 630 / 505 | 630 / 505 | |
54 / 117 | 54 / 117 | 54 / 117 | 54 / 117 | 54 / 117 | 54 / 117 | |
|
|
|
|
|
|
|
Cond. Coil |
|
|
|
|
|
|
Material (Fin/Tube) | Al/Cu | Al/Cu | Al/Cu | Al/Cu | Al/Cu | Al/Cu |
Coil type | RTPF | RTPF | RTPF | RTPF | RTPF | RTPF |
Rows / FPI | 2 / 17 | 2 / 17 | 2 / 17 | 3 / 17 | 2 / 17 | 2 / 17 |
Total face area (ft2) | 17.5 | 17.5 | 25.1 | 31.8 | 23.5 x 2 | 25.0 x 2 |
|
|
|
|
|
|
|
Cond. fan / motor |
|
|
|
|
|
|
Qty / Motor drive type | 2 / direct | 2 / direct | 2 / direct | 2 / direct | 3 / direct | 4 / direct |
Motor HP / RPM | 1/4 / 1100 | 1/4 / 1100 | 1/4 / 1100 | 1/4 / 1100 | 1/4 / 1100 | 1/4 / 1100 |
Fan diameter (in) | 22 | 22 | 22 | 22 | 22 | 22 |
Nominal Airflow (cfm) | 6,000 | 6,000 | 6,000 | 6,000 | 9,000 | 12,000 |
Watts (total) | 610 | 610 | 610 | 610 | 970 | 1150 |
* Approximate system charge with about 25 ft piping of sizes indicated with matched 524J
6