569J 12-14 PIPING RECOMMENDATIONS (TWO-CIRCUIT UNIT)

NOTE: 569J requires TWO sets of refrigeration piping

R---410A

Equivalent Length

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ft

 

0--- 38

38--- 75

75

--- 113

 

113--- 150

150--- 188

 

 

 

 

 

 

 

 

 

 

 

 

 

m

 

0--- 12

12--- 23

23

--- 34

 

34--- 46

 

46--- 57

 

 

 

 

 

 

 

 

 

 

 

 

 

Linear Length

 

 

 

 

 

 

 

 

 

 

Ft

 

0--- 25

25--- 50

50

--- 75

 

75--- 100

 

100--- 125

Model

m

 

0--- 8

8--- 15

15

--- 23

 

23--- 30

 

30--- 38

 

569J*12

Liquid Line

3/8

3/8

3/8

1/2

3/8

1/2

3/8

1/2

 

Max Lift (ft)

 

 

 

 

 

 

 

 

 

 

Novation

25

50

28

 

75

DNU

100

DNU

99

 

RTPF

25

50

75

 

NR

83

100

62

125

 

 

 

 

 

 

 

 

 

 

 

Suction Line

7/8

7/8

1 1/8

 

1 1/8

 

1 1/8

 

 

Charge (lbs) (ea circuit)

 

 

 

 

 

 

 

 

 

 

Novation

7.1

8.1

9.6

11.9

DNU

13.8

DNU

15.8

 

RTPF

13.3

14.3

15.8

NR

16.9

20.0

18.1

22.0

 

 

 

 

 

 

 

 

 

 

569J*14

Liquid Line

3/8

3/8

3/8

1/2

3/8

1/2

3/8

1/2

 

Max Lift (ft)

 

 

 

 

 

 

 

 

 

 

Novation

25

50

48

 

75

DNU

100

DNU

122

 

RTPF

25

50

75

 

NR

54

100

45

125

 

 

 

 

 

 

 

 

 

 

 

Suction Line

7/8

7/8

1 1/8

 

1 1/8

 

1 1/8

 

 

Charge (lbs) (ea circuit)

 

 

 

 

 

 

 

 

 

 

Novation

9.7

10.7

14.5

 

DNU

16.4

DNU

18.4

 

RTPF

23.0

24.0

27.8

NR

26.6

29.7

27.8

31.7

 

 

 

 

 

 

 

 

 

 

 

 

Legend:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Equivalent

Equivalent tubing length, including effects of refrigeration specialties devices

 

 

 

 

 

Length

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Linear Length

Linear tubing length, feet

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid Line

Tubing size, inches OD.

 

 

 

 

 

 

 

 

 

 

 

 

 

Max Lift

Maximum liquid lift (indoor unit ABOVE outdoor unit only), at maximum permitted liquid line pressure drop

 

 

 

S

Linear Length Less than 75 ft (23 m): Minimum 2.0° F subcooling entering TXV

 

 

 

 

 

S

Linear Length Greater than 75 ft (23m): Minimum 0.5° F subcooling entering TXV

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Suction Line

Tube size, inches OD

 

 

 

 

 

 

 

 

 

 

See highlighted: Do not use with RTPF coil model

 

 

 

 

 

 

 

 

 

Charge

Charge Quantity, lbs. Calculated for both liquid line sizes (where applicable), but only with larger suction line size (where

 

applicable)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DNU

Do Not Use (pressure drop exceeds available subcooling in this model)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NR

Not Recommended (use smaller liquid tube size)

 

 

 

 

 

 

 

 

 

NOTE:

For applications with equivalent length greater than 188 ft (57 m) and/0r linear length greater than 125 ft (38 m), contact

 

your local Carrier representative.

 

 

 

 

 

 

 

 

569J

51

Page 51
Image 51
Bryant manual 569J 12-14 Piping Recommendations TWO-CIRCUIT Unit, Model 569J*12