569J 12-14  PIPING RECOMMENDATIONS (TWO-CIRCUIT  UNIT)
NOTE: 569J requires TWO sets of refrigeration piping
Equivalent Length  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | ||
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | ||
  | Ft  | 
  | 75  | 
  | |||||||
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | m  | 
  | 23  | 
  | 
  | 
  | |||||
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | |
  | Linear Length  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | |
  | Ft  | 
  | 50  | 
  | 
  | ||||||
Model | m  | 
  | 15  | 
  | 
  | 
  | |||||
569J*12 | Liquid Line  | 3/8  | 3/8  | 3/8  | 1/2  | 3/8  | 1/2  | 3/8  | 1/2  | ||
  | Max Lift (ft)  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | |
  | Novation  | 25  | 50  | 28  | 
  | 75  | DNU  | 100  | DNU  | 99  | |
  | RTPF  | 25  | 50  | 75  | 
  | NR  | 83  | 100  | 62  | 125  | |
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | ||
  | Suction Line  | 7/8  | 7/8  | 1 1/8  | 
  | 1 1/8  | 
  | 1 1/8  | 
  | ||
  | Charge (lbs) (ea circuit)  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | |
  | Novation  | 7.1  | 8.1  | 9.6  | 11.9  | DNU  | 13.8  | DNU  | 15.8  | ||
  | RTPF  | 13.3  | 14.3  | 15.8  | NR  | 16.9  | 20.0  | 18.1  | 22.0  | ||
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | ||
569J*14 | Liquid Line  | 3/8  | 3/8  | 3/8  | 1/2  | 3/8  | 1/2  | 3/8  | 1/2  | ||
  | Max Lift (ft)  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | |
  | Novation  | 25  | 50  | 48  | 
  | 75  | DNU  | 100  | DNU  | 122  | |
  | RTPF  | 25  | 50  | 75  | 
  | NR  | 54  | 100  | 45  | 125  | |
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | ||
  | Suction Line  | 7/8  | 7/8  | 1 1/8  | 
  | 1 1/8  | 
  | 1 1/8  | 
  | ||
  | Charge (lbs) (ea circuit)  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | |
  | Novation  | 9.7  | 10.7  | 14.5  | 
  | DNU  | 16.4  | DNU  | 18.4  | ||
  | RTPF  | 23.0 | 24.0 | 27.8 | NR  | 26.6 | 29.7 | 27.8  | 31.7 | ||
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
Legend:  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
Equivalent  | Equivalent tubing length, including effects of refrigeration specialties devices  | 
  | 
  | 
  | 
  | 
  | |||||
Length  | 
  | 
  | 
  | 
  | 
  | ||||||
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | |
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | |
Linear Length  | Linear tubing length, feet  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | |
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | |
Liquid Line  | Tubing size, inches OD.  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | |
  | 
  | 
  | 
  | ||||||||
Max Lift  | Maximum liquid lift (indoor unit ABOVE outdoor unit only), at maximum permitted liquid line pressure drop  | 
  | 
  | ||||||||
  | S  | Linear Length Less than 75 ft (23 m): Minimum 2.0° F subcooling entering TXV  | 
  | 
  | 
  | 
  | |||||
  | S  | Linear Length Greater than 75 ft (23m): Minimum 0.5° F subcooling entering TXV  | 
  | 
  | 
  | 
  | |||||
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | |
Suction Line  | Tube size, inches OD  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | |
  | See highlighted: Do not use with RTPF coil model  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | |||
  | 
  | ||||||||||
Charge  | Charge Quantity, lbs. Calculated for both liquid line sizes (where applicable), but only with larger suction line size (where  | ||||||||||
  | applicable)  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | |
  | 
  | 
  | 
  | 
  | 
  | 
  | |||||
DNU | Do Not Use (pressure drop exceeds available subcooling in this model)  | 
  | 
  | 
  | 
  | 
  | |||||
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | |||
NR  | Not Recommended (use smaller liquid tube size)  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | |||
  | 
  | ||||||||||
NOTE:  | For applications with equivalent length greater than 188 ft (57 m) and/0r linear length greater than 125 ft (38 m), contact  | ||||||||||
  | your local Carrier representative.  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | ||
569J
51