569J 12-14 PIPING RECOMMENDATIONS (TWO-CIRCUIT UNIT)
NOTE: 569J requires TWO sets of refrigeration piping
Equivalent Length |
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| ||
| Ft |
| 75 |
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
| m |
| 23 |
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
| |
| Linear Length |
|
|
|
|
|
|
|
|
| |
| Ft |
| 50 |
|
| ||||||
Model | m |
| 15 |
|
|
| |||||
569J*12 | Liquid Line | 3/8 | 3/8 | 3/8 | 1/2 | 3/8 | 1/2 | 3/8 | 1/2 | ||
| Max Lift (ft) |
|
|
|
|
|
|
|
|
| |
| Novation | 25 | 50 | 28 |
| 75 | DNU | 100 | DNU | 99 | |
| RTPF | 25 | 50 | 75 |
| NR | 83 | 100 | 62 | 125 | |
|
|
|
|
|
|
|
|
|
| ||
| Suction Line | 7/8 | 7/8 | 1 1/8 |
| 1 1/8 |
| 1 1/8 |
| ||
| Charge (lbs) (ea circuit) |
|
|
|
|
|
|
|
|
| |
| Novation | 7.1 | 8.1 | 9.6 | 11.9 | DNU | 13.8 | DNU | 15.8 | ||
| RTPF | 13.3 | 14.3 | 15.8 | NR | 16.9 | 20.0 | 18.1 | 22.0 | ||
|
|
|
|
|
|
|
|
|
| ||
569J*14 | Liquid Line | 3/8 | 3/8 | 3/8 | 1/2 | 3/8 | 1/2 | 3/8 | 1/2 | ||
| Max Lift (ft) |
|
|
|
|
|
|
|
|
| |
| Novation | 25 | 50 | 48 |
| 75 | DNU | 100 | DNU | 122 | |
| RTPF | 25 | 50 | 75 |
| NR | 54 | 100 | 45 | 125 | |
|
|
|
|
|
|
|
|
|
| ||
| Suction Line | 7/8 | 7/8 | 1 1/8 |
| 1 1/8 |
| 1 1/8 |
| ||
| Charge (lbs) (ea circuit) |
|
|
|
|
|
|
|
|
| |
| Novation | 9.7 | 10.7 | 14.5 |
| DNU | 16.4 | DNU | 18.4 | ||
| RTPF | 23.0 | 24.0 | 27.8 | NR | 26.6 | 29.7 | 27.8 | 31.7 | ||
|
|
|
|
|
|
|
|
|
|
|
|
Legend: |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Equivalent | Equivalent tubing length, including effects of refrigeration specialties devices |
|
|
|
|
| |||||
Length |
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| |
Linear Length | Linear tubing length, feet |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| |
Liquid Line | Tubing size, inches OD. |
|
|
|
|
|
|
|
|
| |
|
|
|
| ||||||||
Max Lift | Maximum liquid lift (indoor unit ABOVE outdoor unit only), at maximum permitted liquid line pressure drop |
|
| ||||||||
| S | Linear Length Less than 75 ft (23 m): Minimum 2.0° F subcooling entering TXV |
|
|
|
| |||||
| S | Linear Length Greater than 75 ft (23m): Minimum 0.5° F subcooling entering TXV |
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
| |
Suction Line | Tube size, inches OD |
|
|
|
|
|
|
|
|
| |
| See highlighted: Do not use with RTPF coil model |
|
|
|
|
|
|
| |||
|
| ||||||||||
Charge | Charge Quantity, lbs. Calculated for both liquid line sizes (where applicable), but only with larger suction line size (where | ||||||||||
| applicable) |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
| |||||
DNU | Do Not Use (pressure drop exceeds available subcooling in this model) |
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
| |||
NR | Not Recommended (use smaller liquid tube size) |
|
|
|
|
|
|
| |||
|
| ||||||||||
NOTE: | For applications with equivalent length greater than 188 ft (57 m) and/0r linear length greater than 125 ft (38 m), contact | ||||||||||
| your local Carrier representative. |
|
|
|
|
|
|
|
|